Section 5.  Programming the Datalogger
5-23
– see ‘SDM Port’ in Section 1 for details. This should be connected to control port
8 for this example.
A typical  filter that could be used is as follows:
fltst 200 "t[data]A5xff"
This filter works as follows:
t[data] – this filter waits for an exact string match before it starts the next filter. In
this case it is waiting for the sensor to send the string ‘data’.
A5 – this filter sets up a 250ms filter time out. This time out should be long
enough for the sensor to transmit all of its data.
x – this filter marks the start of the data set. In this case the data set is two floating
point numbers.
f – this filter searches for the first ASCII floating point number to convert.
f – this filter searches for the second ASCII floating point number to convert.
*Table 1 Program
  01: 2         Execution Interval (seconds)
;set control port 8 to i/p so it can be used as an interrupt
1:  Set Port(s) (P20)
 1: 8999     C8..C5 = input/nc/nc/nc
 2: 9999     C4..C1 = nc/nc/nc/nc
;do filter setup only if flag one is clear
2:  If Flag/Port (P91)
 1: 21       Do if Flag 1 is Low
 2: 30       Then Do
;set up string filter
3:  SDM-SIO4 (P113)
 1: 1        Reps
 2: 0        Address
 3: 1        Send/Receive Port 1
 4: 2054     Command
 5: 9200     1st Parameters
 6: 0        2nd Parameters
 7: 0        Values per Rep
 8: 0        Loc [ _________ ]
 9: 1.0      Mult
10: 0.0      Offset
;delay required by filter setup command
4:  Excitation with Delay (P22)
 1: 1        Ex Channel
 2: 0        Delay W/Ex (units = 0.01 sec)
 3: 1        Delay After Ex (units = 0.01 sec)
 4: 0        mV Excitation
;set flag one high so the filter set-up is only done once
5:  Do (P86)
 1: 11       Set Flag 1 High