Input Point Module (AFI5100) 
1.8 LEDs 
 
The following table describes the operation of the LEDs located on the AFI5100 : 
 
LED Brief 
Description 
POWER 
The POWER led is illuminated when power has been applied to the device. 
ACTIVITY 
The ACTIVITY led indicates that the AFI5100 is accessing information con-
tained in its internal database or performing a routine operation. 
This LED also indicates whether the initial instruction set has been downloaded. 
If power is applied and the LED blinks quickly, the AFI5100 instruction set (firm-
ware) needs to be downloaded. If the LED is blinking slowly, approximately 
once per second, a firmware set has already been downloaded. 
Tx COMMS 
The Transmission COMMS LED flashes when the IPM is sending data to the 
ACC to which it has been connected (via an FLN). 
Rx COMMS 
The Transmission COMMS LED flashes when the IPM is receiving data from 
the ACC to which it has been connected (via an FLN). 
Inputs  
The tricolor Input Port LEDs indicate the current status of the input port. See the 
table below for an explanation of the colors. 
Outputs 
Each Output Relay has a corresponding LED that is illuminated when the relay 
is activated. 
Fire  
The Fire LED is illuminated when Fire Over-ride is activated. 
 
Each input LED may be in one of two states as indicated by color.  
 
LED Color 
Input status 
Fire Over-ride status 
Green 
Denotes input Normal: Closed 
Denotes FOR Normal: Closed 
Orange 
Denotes input Normal: Open 
Denotes FOR Normal: Open (alarm) 
10
 
Siemens Building Technologies
 
 
Fire Safety & Security Products 
 