Siemens AFI5100 Manual Do Utilizador

Página de 14
Input Point Module (AFI5100) 
1.7 
Links and Jumpers 
 
The following table outlines the link settings for the AFI5100 : 
 
Link Description 
Value 
LK1, LK2 
Links 1 and 2 are used to configure 
whether Fire Over-ride (FOR) will oper-
ate in Enhanced FOR mode or Normal. 
Enhanced mode also requires the 
connection of a supervision circuit to 
the Fire Over-ride Input. 
To enable Normal 
Mode: 
LK1 LK2
N
O
R
M
A
L
F
O
R
 
To enable En-
hanced Mode: 
LK1 LK2
 
N
O
R
M
A
L
F
O
R
LK4, LK6 
Links 4 and 6 control whether Fire 
Over-ride (FOR) is enabled. 
If the links are set to FOR operation, 
activation of the FOR input will cause 
the outputs to return to the NO position.
If the links are set to the off position, 
FOR input will have no effect on the 
state of the output relays. 
FOR operation 
active: 
LK4 LK6
 
F
O
R
E
N
A
B
L
E
 
FOR operation 
ignored: 
E
N
A
B
L
E
LK4 LK6
 
F
O
R
LK3, LK5 
These auxiliary links have been included for further enhancement of the system. 
LK7 
LK7 affects the reset action when the 
RESET link (LK9) is set and the power 
turned on.  
See LK9 below for a description of how 
to reset the unit. 
LK7
 
If the jumper on Link 7 is set as shown, 
it is set to “Full Reset” mode. 
LK7
 
If the jumper on Link 7 is taken off, it is 
set to “Partial Reset” mode. 
LK8 
This is a General Purpose links that has been included for further enhancement 
of the system. 
LK9 
Memory Clear and Reset  
Setting LK9 and turning the power off and on will reset the IPM. A full or partial 
reset can be achieved by setting LK7 on or off.  
If LK7 is set, the IPM will fully reset and any firmware loaded into the memory will 
be erased. You will need to re-program the IPM with firmware again before it can 
operate. 
If LK7 has the jumper removed, the microcontroller will be rebooted but the firm-
ware will remain in memory. 
LK10 
EOL Termination (Bus)  
This link allows the RS485 BUS com-
munications channel to be terminated 
in noisy or lengthy comms. 
Note: Units located at the end of bus 
lines only should have this link set. 
RS485 BUS port 
not terminated. 
LK10
EOL
 
RS485 BUS port 
terminated. 
LK10
EOL
 
LK11 – LK14 
FOR Activation 
These links allow FOR activation to be 
enabled or disabled for each individual 
relay output. 
Enabling Fire Override for a relay 
means that when the FOR input is 
activated, the relay output switch to the 
NO position. 
LK11
 
FOR EN
FOR DIS
LK12
 
In the above diagram LK11 (Relay 1) is 
set to FOR Enabled and LK12  
(Relay 2) is set to FOR Disabled. 
9
 
Siemens Building Technologies
 
 
Fire Safety & Security Products 
 
02.2005