Siemens 125-3584T Manual Do Utilizador
Chapter 5 - Point Commander
Using the Point Commander Application
39
Siemens Industry, Inc.
125-3584T
Error Code
Situation
INVALID_DATATYPE
The data type of the value provided is incorrect
for the specified property.
VALUE_OUT_OF_RANGE
The value provided is outside the range of values
that the property can take on.
NO_SPACE_TO_WRITE_PROPERTY
There is not enough space to store the new
value.
DATATYPE_NOT_SUPPORTED
The data being written has a data type not
supported by the property.
Tips for Using the Point Commander Application
Points can be commanded from the Navigation pane or from an animated graphic.
See the
FINlite Graphics Tool
section for information on commanding a point from
a graphic.
You can only command points if you have been given Command or higher access
level to the point.
– Both analog and digital points can be commanded.
– Generally, only output points (AO, BO, and MSO) or virtual points (AV, BV,
– Both analog and digital points can be commanded.
– Generally, only output points (AO, BO, and MSO) or virtual points (AV, BV,
MSV) can be commanded; however, AI and BI input points can be commanded
if taken out of service first.
If the same point is commanded from two different sessions, the command with the
higher priority will override. If the commands are made with the same priority, the
last command will override the earlier command.
Multi State Input Object (MSI) points are not supported on the FLN.
Use caution when moving the Commander window around the screen. If you move
it too far up the screen, you may not be able to access the title bar and move the
screen back down into view.
Using the Point Commander Application
Commanding Point Values
Commanding a point means using the Point Commander Application to manually
override the system program instructions for either an output point or a virtual input
point. Point commanding changes the command priority from NONE.
This procedure is only available to users with Command or higher access to points.