321 Studios QW5S Manual Do Utilizador

Página de 6
 
F1915 (2012 04) 
 
 
 
Page 4 of 6 
 
The built-in commercial room ventilator  (CRV)  is internally mounted 
and allows outside ventilation air, up to 50% of the total air flow 
rating of the unit, to be introduced through the air inlet openings. The  
CRV shall be modular and easily added or removed from the unit 
cabinet.  It includes a built-in exhaust air damper.   The damper can 
be easily adjusted to control the amount of fresh air supplied into the 
building.  The CRV can be controlled by indoor blower operation or 
field controlled based on room occupancy.  Unit complies with 
ANSI/ASHRAE Standard 62.1 Ventilation for Acceptable Air Quality. 
 
Two Models Available: 
Spring Return on Power Loss or 
Deactivation - Vent Option V 
Power Return (will not close on power loss) 
– Vent Option P 
 
 
 
4.4
 
ENERGY RECOVERY VENTILATOR 
 
       OPTIONAL
 
The Energy Recovery Ventilator (ERV) shall consist of 1 or 2 rotary 
wheels in an insulated cassette frame with seals, drive motor and 
belt. The ERV assembly shall also include intake and exhaust 
blowers. The entire assembly shall easily slide in or out of the unit 
cabinet, allowing for maintenance or replacement. The total energy 
wheel shall be coated with silica gel desiccant, permanently bonded 
without the use of binders or adhesives. The coated segments shall 
be washable with detergent or alkaline coil cleaner and water. 
Desiccant shall not dissolve or deliquesce in the presence of water 
or high humidity.  All diameter and perimeter seals shall be provided 
as part of the cassette assembly and shall be factory set. Drive belts 
shall not require external tensioners or adjustment. Cassette wheels 
shall include rims to prevent belts from slipping off wheels.   Intake 
and exhaust blowers shall have selections of high, medium or low 
speed and selected independently, to allow for positive 
pressurization if desired. The ERV cassette including parts and 
media shall  include 5year warranty subject to terms and conditions 
of Bard’s warranty. 
   
  
The ERV thermal performance shall be certified by the manufacturer 
in accordance with ASHRAE Standard 84, Method of Testing  Air-to 
Air Heat Exchangers and ARI  Standard 1060, Rating for Air-to-Air 
Energy Recovery Ventilation Equipment Cassettes, and shall be 
listed in the ARI Certified Products.  Unit complies with 
ANSI/ASHRAE Standard 62.1 Ventilation for Acceptable Air Quality. 
.      
 
5.0  FILTER OPTIONS  - (Select One)