2.3  COMPRESSOR 
All models shall use a high efficiency scroll compressor with step 
capacity providing 2 stages of control.  The compressor shall be 
covered by a 5-year parts warranty.  The refrigeration circuit shall be 
equipped with factory installed high and low-pressure controls.   The 
refrigeration control shall be a factory installed TXV. Compressor 
shall be mounted on isolation rails with double grommets.  Unit shall 
be provided with R-410A (HFC) non-ozone depleting refrigerant. Unit 
shall be provided with liquid line filter/drier.   
 
 
Current sensing relay shall be used to detect high amps caused by 
high ambient and/or low voltage and to shift compressor to 1
st
-stage 
operation until conditions corrected 
 
             
2.4  COAXIAL WATER COIL 
All models shall have  either  cupronickel  or copper (SELECT ONE); 
water coil, fully insulated, with double o-ring  connections.  Copper 
coils should not be used on open wells.  
 
2.6  INDOOR BLOWER MOTOR 
The indoor blower motor shall be a variable speed (ECM) type to 
produce the same rated airflow from 0 to .8 inch WC of external static 
pressure (.5 on Q24W model) at low sound levels.  The motor is to be 
self-adjusting to provide proper rated airflow at high static pressures 
without user adjustment or wiring changes by the user.  The motor 
shall be programmed for 20-second ramp up and 60-second down 
rate for quiet, smooth starting and stopping.  ECM motor shall 
include preprogrammed speeds for ventilation mode, first stage 
operation, second stage operation, ducted operation, and non-
ducted operation.  
 
2.7  ELECTRICAL COMPONENTS 
Electrical components are easily accessible for routine inspection 
and  maintenance through front service panels.  Circuit breaker is 
standard on all 208/230-volt models and rotary disconnect standard 
on all 460-volt models.  Circuit breaker/rotary disconnect access is 
through lockable access panel.  Lock and key are provided  as 
standard equipment.  Unit shall have single point entry for line 
voltage.  
 
2.8
 
CONTROL CIRCUIT 
 
The internal control circuit shall consist of a current limiting 24VAC 
type  65VA  transformer  with circuit breaker. To prevent rapid 
compressor short cycling, a five-minute time delay circuit shall be 
factory installed. Two low-pressure controls shall be included as