321 Studios QW2S Manual Do Utilizador

Página de 6
 
F1915 (2012 04) 
 
 
 
Page 3 of 6 
 
standard. One shall be used for fresh water applications, the other 
for protected (antifreeze) closed systems. The factory wired switch is 
for fresh water.  
 
Phase rotation protection and phase failure protection shall be 
standard factory installed features on all equipment with three-phase 
power. If unit is wired incorrectly phase monitor will lock out 
compressor operation and red warning light shall energize. Once 
power wiring is corrected at field power wiring location, a green light 
will energize on phase monitor. If a phase of power is lost, the phase 
monitor will also lock out.   
 
 
 
2.9
  SERVICE FEATURES 
The unit shall include a diagnostic light to indicate when service is 
required.  System Service
  shall detect high or low-pressure control 
operation
 
 
 
 
 
 
3.0   LOOP MODULE PUMPING SYSTEM 
All models shall be designed with mounting and wiring provisions 
for  field installed pump module option, when unit is applied with 
ground loop system. 
 
4.0  VENTILATION OPTIONS (Select One) 
 
Q-Tec models are designed to provide optional ventilation packages to 
meet all of your ventilation and indoor air quality requirements.  All 
ventilation packages are factory installed. 
 
4.1  BAROMETRIC FRESH AIR DAMPER   
      STANDARD 
The barometric fresh air damper is a standard feature on all models.  
It allows outside ventilation air, up to 25% of the total airflow rating 
of the unit, to be introduced through the air inlet openings and to be 
mixed with the conditioned air.  The damper opens during blower 
operation and closes when the blower is off.  Adjustable blade stops 
allow different amounts of outside air to be introduced into the 
building and can be easily locked closed if required. 
 
 
4.2  BLANK OFF PLATE   
 
 
 
       OPTIONAL 
A blank off plate covers the air inlet openings, which restrict any 
outside air from entering the unit.  The blank off plate should be 
utilized in applications where outside air is not required to be mixed 
with the conditioned air.  
 
4.3  COMMERCIAL ROOM VENTILATOR   
        OPTIONAL