75
CHAPTER 7 VARIOUS SETTINGS
7
7.3  Offset/Gain Sett
ing
  
7.3
Offset/Gain Setting
When the user range setting is used, configure the offset/gain setting with the following operations.
When factory default settings are used, the offset/gain setting is not required.
1.
Power off the module.
2.
Set "O/G" for "x10" of the station number setting 
switch.
3.
Power on the module to check the LED is in the 
following status.
RUN LED: OFF
O/G LED: ON
4.
Select the setting target using the SET/SEL button.
5.
For the selected channel, adjust the analog output 
value by using the "+" and "–" switches.
Pressing the "+" switch increases the analog output 
value. Pressing the "–" switch decreases the analog 
output value.
6.
Keep pressing the   button until the RUN LED 
turns on.
After the RUN LED turns on, release the   button.
While the RUN LED is on, the offset value or gain value 
is being written to the nonvolatile memory.
After the writing, the RUN LED turns off.
After checking that the RUN LED turns off, go to the 
next step.
7.
When setting another channel, go back to step 4.
8.
After setting all the channels, power off the module.
: OFF
: ON
[User range setting 1 (-10 to 10V)]
CH1: Offset
CH1: Gain 
CH2: Offset
CH2: Gain 
CH3: Offset
CH3: Gain 
CH4: Offset
CH4: Gain 
[User range setting 2 (0 to 20mA)]
CH1: Offset
CH1: Gain 
CH2: Offset
CH2: Gain 
CH3: Offset
CH3: Gain 
CH4: Offset
CH4: Gain 
Button
Button
Data are being written.
The write is completed.
Keep pressing the    button.