3.4.3
CH
[
]
 Time/Count/Moving average/Time constant setting (Un\G1 
to Un\G8)
(1) Time average, count average, moving average or time constant for 
primary delay filter is set for each channel that is specified for averaging 
processing.
(2) The default value is set to "0000
H
".
(3) To activate the setting, turning ON/OFF Operating condition setting 
request (Y9) is required.
(4) The following table shows the settable range.
 * 1 : Values can be set in units of 1ms; however, processing is performed in units of 320ms.
POINT
When a value out of the above setting range is written, an error (error code: 20 , 
30 , 31  or 32 ) occurs on the channel. Then, Error flag (XF) turns ON and 
conversion processing is performed with the setting before the error occurrence.
Table 3.10 Settable range
Processing method
Setting value
Time average
1280 to 5000 (ms)
*1
Count average
4 to 500 (times)
Moving average
2 to 60 (times)
Primary delay filter
320 to 5000 (ms)
*1