Справочник Пользователя для Mitsubishi Electronics Q68RD3-G

Скачать
Страница из 212
3
SPECIFICATIONS
3.4 Buffer Memory
3.4.11 CH[] Offset/gain temperature setting values (Un\G28 to Un\G43)
3
 - 37
1
O
V
ER
VI
E
W
2
SY
STEM
 
CONFIGURA
TION
3
SP
ECIFICA
T
IONS
4
P
R
OC
EDU
R
ES
 A
ND 
SE
TTINGS B
E
FORE
 
SY
STEM
 O
PER
A
T
ION
5
UTIL
ITY P
A
CK
AGE
 
(GX CONFIGURA
T
O
R-TI)
6
P
R
OGRAM
M
ING
7
ONLINE MO
D
U
LE
 
CH
A
N
G
E
8
TR
O
U
B
L
E
S
HOOTING
3.4.11
CH
[
]
 Offset/gain temperature setting values (Un\G28 to Un\G43)
(1) Offset/gain temperature setting values are specified in 16-bit signed 
binary for each channel.
(2) A value is set in units of 0.1 .
(3) When Channel change request (YB) is turned ON in the offset/gain 
setting mode, measured temperature value is compensated for the value 
written in this area.
POINT
(1) High accuracy is ensured for the Offset/gain temperature setting values when 
the minimum/maximum temperatures of the operating range are used to 
compensate errors.
(2) Set the Offset/gain temperature setting values while reading measured 
temperature values.
(3) Satisfy the following conditions when setting the Offset/gain temperature 
setting values.  If the conditions are not satisfied, an error (error code: 41 )  
occurs.
Condition 1: Within the input enabled range
Condition 2:
(Gain temperature setting value) - (Offset temperature setting value) > 0.1[ ]
(4) The offset/gain temperature setting values are stored into the Flash memory 
of the Q68RD3-G using the User range write request (YA), and the values are 
not erased at power-off.
3.4.12
Warning output enable/disable setting (Un\G46)
(1) Enable/disable status of warning output for process alarm or rate alarm 
is set for each channel.
(2) The default value is set to "Disable" for all channels.
(3) To activate the setting, turning ON/OFF Operating condition setting 
request (Y9) is required.
b15
b14 b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
CH4 CH3 CH2 CH1
CH8 CH7 CH6 CH5
CH4 CH3 CH2 CH1
CH8 CH7 CH6 CH5
Rate alarm setting
Process alarm setting
0: Enable, 1: Disable