4   SETTING AND PROCEDURE BEFORE OPERATION 
 
4.10.1 Loop test (optical loop system only) 
This test checks the line status (forward loop or reverse loop) after all stations are 
connected to the optical loop system. 
 
GX Developer
Station
No. 0
Reserved station
Loopback
Faulty station
IN OUT
Loopback
Station
No. 3
IN OUT
Station
No. 6
IN OUT
Station
No. 4
IN OUT
IN
OUT
Station
No. 1
IN
OUT
Station
No. 7
IN
OUT
Station
No. 2
OUT
IN
Station
No. 5
Remote 
master station
 
When the loop test is performed using GX Developer connected to the remote master 
station in the system above, where IN connector and OUT connector of the station 
number 5 are connected inversely, the following screen appears. The station number 5 
is detected as a receive direction faulty station. 
 
 
 
POINT 
 
In the loop test, the wiring status is checked after the data link has been stopped. 
To check the wiring status without stopping the data link, use SW009C to SW009F. 
For details, refer to Section 8.2.9.