Справочник Пользователя для Mitsubishi Electronics QJ71LP21

Скачать
Страница из 400
 
 
 
4 - 35                                                                                                                                                       4 - 35 
MELSEC-Q
4   SETTING AND PROCEDURE BEFORE OPERATION 
 
4.10.3 Station order check test (optical loop system only) 
This test checks the order of connected stations in the optical loop system. 
The following table lists the correspondence between the loop status and the order of 
stations that can be checked in the test. 
 
Loop status 
Display 
Forward and reverse loops 
The station numbers connected in the direction of the forward loop from the host as well as 
the station numbers connected to the direction of the reverse loop from the host 
Forward loop 
Only the station numbers connected in the direction of the forward loop from the host 
Reverse loop 
Only the station numbers connected in the direction of the reverse loop from the host 
Loop back 
Only the station numbers connected in the direction of the forward loop from the host 
 
 
When the station order check test is performed using GX Developer connected to the 
remote master station in the system above, the following screen appears. The result 
shows that the loopback is performed in the stations, the station number 4 and 2, 
connected in the forward loop direction. 
Station No. 3 is 
not displayed 
because it is a 
reserved station.