MELSEC-Q
5   PARAMETER SETTINGS 
 
5.1.6 Valid Module During Other Station Access 
This parameter is used to specify any of the following modules to be relayed when a 
data communication request for which the network No. of the access target 
programmable controller station cannot be specified from the host (access from the 
serial communication module (A compatible 1C frame), Ethernet module (A compatible 
1E frame), etc. to other stations) is issued. 
 
•  CC-Link IE Controller Network, CC-Link IE Field Network, MELSECNET/H, 
MELSECNET/10 module 
• Ethernet module 
 
This setting is not required when a data communication request for which the network 
No. can be specified, such as the serial communication module (QnA compatible 3C 
frame, QnA compatible 4C frame) or Ethernet module (QnA compatible 3E frame), is 
used. Leave it as the default (1) setting. 
For details of the serial communication module or Ethernet module protocol, refer to 
the MELSEC-Q/L MELSEC Communication Protocol Reference Manual. 
 
[Screen settings] 
 
Select from the selection dialogue box.
 
 
(Example) 
In the example below, the personal computer connected to the serial communication 
module can communicate with the station on network No. 2 where the network module 
3 is connected. 
 
Module 1
Valid module during
other station access: 3
A compatible 1C frame
Network No. 1
Network No. 3
Network No. 2
Module 2 Module 3 Module 4
Power 
supply 
module
QX41
QCPU
QY41P
QJ71
LP21
QJ71
E71
-100
QJ71
LP21
QJ71
LP21
QJ71
C24
Ethernet
QX41
QJ71
LP21
QCPU
Power 
supply 
module