5   PARAMETER SETTINGS 
 
5.2 Remote I/O Station Parameter Settings 
For remote I/O stations, set up the PLC parameters, network parameters, and remote 
password on the remote I/O module as needed. 
 
POINT 
 
After writing the parameters to the remote I/O module, reset it to enable the 
parameters that have been set.  To reset the remote I/O module, use the reset 
switch on the module or power OFF and then ON the remote I/O station. 
 
5.2.1 Remote I/O station possible parameter settings 
The following parameters are set as needed on the remote I/O station and written to 
the remote I/O module. 
If settings are not needed, the remote I/O station operates using the remote I/O module 
default settings so there is no need to write the parameters to the remote I/O module. 
 
(1) PLC 
parameters 
The remote I/O module can set the PLC parameters in the same manner as the 
CPU module.  However, only the required items can be set as a remote I/O 
station. 
 
Category Item  Default 
PLC system 
Module synchronization 
Synchronizes intelligent module's pulse 
up 
Selected 
Points occupied by empty slot 
Points occupied by empty slot 
16 points 
PLC RAS 
Error check 
Carry out fuse blown check 
Selected 
Verify module 
Selected 
Operating mode when there is an error 
Fuse blown 
Stop 
Module verify error 
Stop 
Operational settings 
Remote I/O switch setting 
Remote I/O switch setting (For future 
expansion) 
— 
Assignment method 
Points/Start 
Start/End 
Start/End 
Forwarding parameter between devices 
Device name 
Blank 
Points/Start 
Start/End 
I/O assignment 
I/O assignment 
Type 
Blank 
Model name 
Points 
StartXY 
Switch setting 
Switches 1 to 5 
Blank 
Detailed setting 
Error time output 
mode 
Clear 
H/W error time PLC 
operation mode 2 
Stop 
I/O response time 
10ms or 0.2ms 
Standard setting 
Base model name 
Blank 
Power model name 
Extension cable 
Slots 
Base mode 
Auto