Справочник Пользователя для Mitsubishi Electronics QJ71LP21S-25

Скачать
Страница из 400
 
 
 
2 - 3                                                                                                                                                             2 - 3 
MELSEC-Q
2   SYSTEM CONFIGURATION 
 
(2)  Table 2.2 lists the setting items on the remote I/O module of the remote I/O 
station (R) and the parameter setting items on GX Developer. 
 
Table 2.2  Remote I/O station setting items 
Setting items 
Remote I/O station (R) 
Reference 
Network module switch 
 
STATION NO. 
1 to 64 
Section 4.2.2 
 MODE 
 
Section 4.2.2 
Parameter setting on GX Developer 
 PLC 
system 
 
 PLC 
RAS 
 
 I/O 
assignment 
 Operation 
setting 
Section 5.2.1 
 Ethernet 
setting 
 CC-Link 
setting 
 
Remote password setting 
 
Section 7.12 
GX Configurator setting 
 Initial 
setting 
 
Section 5.2.1(4)
 
Auto refresh setting 
 
Section 5.2.1(4)
: Always set,  : Default setting,  : Set as needed,  : No need to set 
 
4 : Refer to the User's Manual (Function Explanation, Program Fundamentals) for 
the CPU module used. 
5 : Refer to the Q Corresponding Ethernet Interface Module User's Manual (Basic) 
(SH-080009). Note that interrupt setting is not available. 
6 : Refer to the MELSEC-Q CC-Link System Master/Local Module User's Manual 
(SH-080394E). Note that interrupt setting is not available. 
 
2.1.3 Available device ranges 
The remote I/O network can use the following device ranges within each network 
module.  
These device ranges indicate the remote master station. 
 
Device Range 
setting 
Other 
LB 0
H
 to 3FFF
H
 (16384 points)
— 
LW 0
H
 to 3FFF
H
 (16384 points)
LX 0
H
 to 1FFF
H
 (8192 points)  The device range (excluding that of I/O module mounted on the host 
station) should be assigned to each network module. 
LY 0
H
 to 1FFF
H
 (8192 points) 
 
: Available device range
B/W
X/Y
Actual I/O
LX/LY
CPU module
LB/LW
CPU module
Extended     1
0
3FFF
H
2000
H
3000
H
(4096)
1000
H
(8192)
(12288)
(16383)
Network module
Network module
1: Expandable by changing from [PLC parameters] - [Device settings]