450260-1
www.amdry.com
13
Burner  Air  Switch
The dryer uses a burner air switch on its burner components.
The  differential  air  pressure  is  measured  by  this  air  switch,
which is located next to the burner fan motor.  If the combustion
air is inadequate, this switch will prevent ignition.  The setting
of  this  burner  air  switch  is  adjustable,  and  is  preset  at  the
factory.
When the pilot flame is ignited, the pilot gas pressure should
measure  3.5-inches  (38.1  mm)  water  column  (W.C.)  for
natural gas and 1.5-inches (88.9 mm) W.C. for liquid propane
(L.P.)  gas.    The  pilot  flame  should  be  about  the  size  of  a
3-inch  diameter  ball.
Once  the  pilot  has  been  properly  set,  remove  the  pressure
gauge from the pilot line connect a differential pressure gauge
between  the  main  gas  pressure  tap  (HI  port)  and  the  air
pressure tap (LO port) on the side of the gas burner box.  The
lines  connecting  the  gauge  to  these  taps  must  be  long
enough to allow the gauge to sit outside of the dryer so that
the burner section access door can be closed when the dryer
runs.  Running the dryer with these doors open will give an
incorrect  air  pressure  reading.
MAN4398
Once this differential gauge is installed, open the main gas
shutoff valve and push the test and reset button on the BCM
so that the button springs out.  Restart the dryer.  The ignition
process should now continue to the full gas flow state.  The
differential gauge should read 2.5-inches (63.5 mm) W.C. for
natural gas and 1.25-inches (31.8 mm) W.C. for L.P. gas.  If it
does  not,  adjust  the  top  gas  valve  as  described  in  “Top
Motorized Gas Valve” on page 11.
Burner Air Switch Replacement
1. Discontinue electrical service to the dryer.
2. Remove  the  two  (2)  1/4"  x  1/8"  M.P.T.  straight  brass
connectors from the burner fan air switch.
3. Remove  the  5/16-18  x  3/4"  tap  bolt  as  well  as  the
5/16" lock washer.
4. Mark and identify the wires for correct replacement on
the new burner air switch.
5. Remove the cord grip from the burner fan air switch.
6. To install new burner air switch, reverse Step #5 through
Step #2.
7. Reestablish electrical service to the dryer.
Burner  Squirrel  Cage  Fan  Components
The combustion air is produced by a 6-1/4" squirrel cage fan,
attached  to  a  1-1/2  hp,  3,600  rpm  motor.   This  motor  must
spin counterclockwise (CCW) as viewed from the rear of the
motor.