C
 
01   Enter Zn No.
 
 12 
 
Zone Number   
Press [
✱] to continue. 
 
(prompt appears
 
if zone number was selected) 
Enter the desired zone number associated with this output 
number. At the ENTER EVENT prompt, enter the zone event 
that will activate this output. 
01 Enter Event   
0 = restore; 1 = alarm/fault/trouble 
Restore 0   
Press [
✱] to continue to the “Output Action” prompt
 
 
 
 
01 Output Action
 
Close for 2 sec 
 
Output Action 
0 = off  
1 = Close for 2 seconds 
2 = Stay Closed  
3 = Pulse on & off (1 sec 
ON, 1 sec OFF) 
4 = Change Device State 
5 = Duration 1 (see data 
field *177) 
6 = Duration 2 (see data 
field *177) 
Press [
✱] to continue. 
Enter the desired device action. 
 
 
 
 
Enter Output No.
 
R02 02 
 
Output Number 
01-16 = FA168CPS outputs 
01-08 = FA148CP outputs 
17-18 = on-board triggers 
Press [
✱] to continue.
 
Enter the device output number (programmed in *79 Menu 
Mode) you want associated with this output.
 
 
 
 
02    A   E   P   TRIG
 
R02  1   1    3  ZL=00 
 
Summary Screen 
Press [
✱] to continue.
 
 
A summary screen appears showing the programmed settings. 
Press [
∗] to return to OUTPUT FUNCTION NUMBER prompt
 
 
 
 
∗∗∗∗81 ZONE LIST MENU MODE  
(press *81 while in Programming mode)  The Zone List Worksheet is on page Error! Bookmark not defined.
Zone lists let you group individual zones for use with certain system actions. Using this mode, simply select an appropriate 
zone list number, then add the desired zone numbers to be included in that list. 
The following table shows the available zone lists and their purposes: 
List No. 
Used for… 
Notes 
1, 2 
general purpose (GP) 
3 chime-by-zone 
(see field *26 to enable option)
 
cross zones (see note at right) 
night stay zones 
general purpose  
SIA-Compliant
: dial delay disable 
7 general 
purpose 
SIA-Compliant
: unlimited reports 
8 general 
purpose 
zones that activate Pager 1 
10 
zones that activate Pager 2 
11 
zones that activate Pager 3 (FA168CPS) 
12 
zones that activate Pager 4 (FA168CPS) 
•  Any list may include any or all of the system's zone numbers. 
•  A zone list can be assigned to more than one output relay. 
•  Zone List 4: When creating zone list 4 for cross zoning, 
include only zones assigned to zone types 3, 4, or 5. Do not 
include zones that have delays (entry/exit zones, interior 
w/delay) or 24-hour zones, as these zone types may produce 
unpredictable operation and may not function as intended.
 
See field *85 for Cross Zone Timer option. 
•  Zone List 6: 
SIA-Compliant
:
 
See field *50 for Dial Delay Disable 
option. 
•  Zone List 7: 
SIA-Compliant
See field *93 for Unlimited Reports 
option. 
 
*81 Menu Mode 
 
 
 
Zone List No.
 
(00 = Quit) 
01 
 
Zone List Number 
01-12 = zone list number 
[
∗] to continue
 
Enter the Zone List Number to program (or 00 to quit). Press [
✱] 
to advance. 
In the following displays, zone list 01 has been selected.
 
 
 
 
01  Enter Zn Num.
 
(00 = Quit) 
00 
 
Zone Number 
01-64† = zone numbers 
followed by [
∗] to 
accept each zone  
00 to continue
 
Enter each zone number to add to the zone list, followed by 
pressing [
✱] (example, 01✱, 02✱, 03✱). After all zones are 
entered, press 00 to continue. 
IMPORTANT: Do not include fire zones in zone lists that are 
used to STOP device actions. 
† FA168CPS = 01-64; FA148CP = 01-06, 09-34, 49-56.
 
 
 
 
01 Del Zn List?
 
0 = No  1 = Yes 
 
Deleting Zone Lists 
0 = don’t delete list 
1 = delete this zone list 
[
∗] to continue
 
To delete the zone list, enter 1. All zones in the zone list will be 
deleted automatically and the system returns to the Zone List 
No. prompt. 