Chapter 10  High-Level Positioning Control 
 
10.6 Start program for high-level positioning control 
10.6.1 Starting high-level positioning control 
To execute high-level positioning control, a sequence program must be created to start 
the control in the same method as for major positioning control.   
 
The following shows the procedure for starting the "1st point block start data" 
(regarded as block No. 7000) set in axis 1. 
 
 
[QD77MS4 use] 
 
1500
Y10
1501
PLC CPU
7000
1
ON
QD77MS
Input/output signal 
 
Servo amplifier
 
Buffer memory  
Control by designated
positioning data
 
 
   When carrying out a positioning start with the
   next scan after a positioning operation is 
   completed, input signal X10 as an interlock so
   that the start is carried out once the X10 signal
   turns OFF after the Y10 signal turns OFF. 
 
1)
3)
2)
4)
1) Set "7000" in " Cd. 3 Positioning start No.".
    (This establishes that the control as "high-level positioning control" using block start data.)
2) Set the point No. of the "block start data" to be started. (In this case "1".)
3) Turn ON the start signal.
4) The positioning data set in the "1st point block start data" is started. 
                                                                                                                               
 
 
(Note): Refer to Chapter 5 for buffer memory address of QD77MS16.
 
Fig. 10.2 High-level positioning control start procedure