10 - 27 
Chapter 10  High-Level Positioning Control 
 
10.6.2 Example of a start program for high-level positioning control 
The following shows an example of a start program for high-level positioning control in 
which the 1st point "block start data" of axis 1 is started. (The block No. is regarded as 
"7000".) 
 
  Control data that require setting 
 
The following control data must be set to execute high-level positioning control. 
The setting is carried out using a sequence program.   
 
Setting item 
Setting 
value 
Setting details 
Buffer memory address
QD77MS2 
QD77MS4 
QD77MS16
[Cd.3] Positioning 
start 
No.  7000 
Set "7000" to indicate control using "block 
start data". 
1500+100n 4300+100n
[Cd.4] 
Positioning starting 
point No. 
Set the point No. of the "block start data" to 
be started. 
1501+100n 4301+100n
 
n: Axis No.-1 
(Note): Refer to Section 5.7 "List of control data" for details on the setting details. 
 
 Start conditions 
 
The following conditions must be fulfilled when starting the control. The required 
conditions must also be integrated into the sequence program, and configured so 
the control does not start unless the conditions are fulfilled.   
 
Signal name 
Signal state 
Device 
QD77MS2 
QD77MS4 
QD77MS16 
Interface 
signal 
PLC READY signal 
ON PLC CPU preparation completed
Y0 
READY signal 
ON QD77MS preparation completed
X0 
All axis servo ON 
ON All axis servo ON 
Y1 
Synchronization flag 
ON
QD77MS buffer memory 
The access is possible. 
X1 
Axis stop signal 
OFF Axis stop signal is OFF 
Y4 to Y7 
[Cd.180] Axis stop
Start complete signal 
OFF Start complete signal is OFF 
X10 to X13 
[Md.31] Status: b14
BUSY signal 
OFF BUSY signal is OFF 
XC to XF 
X10 to X1F 
Error detection signal 
OFF There is no error 
X8 to XB 
[Md.31] Status: b13
M code ON signal 
OFF M code ON signal is OFF 
X4 to X7 
[Md.31] Status: b12
External 
signal 
Forced stop input signal  ON There is no forced stop input 
– 
Stop signal 
OFF Stop signal is OFF 
– 
Upper limit (FLS) 
ON Within limit range 
– 
Lower limit (RLS) 
ON Within limit range 
–