Справочник Пользователя для Avaya 03-300430
Communication Manager Maintenance-Object Repair Procedures
2064 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
106
FAIL
The SNI circuit pack cannot communicate with the SNI in slot 6 over the
circuit path.
circuit path.
1. Fix any on-board SNI-BD errors against this SNI and the SNI in slot 6.
Use display errors to find any SNI-BD errors and check
display alarms to see if the errors have on-board alarms. Then
display alarms to see if the errors have on-board alarms. Then
follow the repair procedures for SNI-BD.
2. Use display errors to check the error log for other SNI circuit
packs with SNI-PEER Error Type 1025. If other SNI circuit packs have
SNI-PEER Error Type 1025, then replace the SNI in slot 6. Replacing
an SNI may be service interrupting. See the SNI-BD section for the
procedure for replacing an SNI.
SNI-PEER Error Type 1025, then replace the SNI in slot 6. Replacing
an SNI may be service interrupting. See the SNI-BD section for the
procedure for replacing an SNI.
If other SNI circuit packs do not have SNI-PEER Error Type 1025 errors,
the problem could be at either of the peer SNI boards. It is arbitrary as to
which SNI is replaced first. Proceed as follows:
3. Replace this SNI.
4. Replace the SNI in slot 6.
107
FAIL
The SNI circuit pack cannot communicate with the SNI in slot 7 over the
circuit path.
circuit path.
1. Fix any on-board SNI-BD errors against this SNI and the SNI in slot 7.
Use display errors to find any SNI-BD errors and check
display alarms to see if the errors have on-board alarms. Then
display alarms to see if the errors have on-board alarms. Then
follow the repair procedures for SNI-BD.
2. Use display errors to check the error log for other SNI circuit
packs with SNI-PEER Error Type 1281. If other SNI circuit packs have
SNI-PEER Error Type 1281, then replace the SNI in slot 7. Replacing
an SNI may be service interrupting. See
SNI-PEER Error Type 1281, then replace the SNI in slot 7. Replacing
an SNI may be service interrupting. See
page 2046 for the procedure for replacing an SNI.
If other SNI circuit packs do not have SNI-PEER Error Type 1281 errors,
the problem could be at either of the peer SNI boards. It is arbitrary as to
which SNI is replaced first. Proceed as follows:
3. Replace this SNI.
4. Replace the SNI in slot 7.
Table 749: TEST #755 SNI Circuit Path Test (continued)
Error
Code
Code
Test
Result
Result
Description / Recommendation
5 of 11