Server Alarms
92 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
1. These events will degrade the server’s state of health.
System Technician-Demanded Tests:
Descriptions and Error Codes
Descriptions and Error Codes
This MO provides no on-demand tests for system technicians.
Back to:
Back to:
UPS Alarms to the Media Server
S8700 | 8710
/
S8500
/
S8300
alarms and their troubleshooting procedures.
Trap (3) –
upsAlarmGeneralFault
#1,ACT,UPS,A,27,WRN,Miscellaneous trap, e.g., bad
battery
(For troubleshooting procedures, see Event #
(For troubleshooting procedures, see Event #
Table 25: Enterprise-Specific UPS Traps to Server (continued)
SNMP Trap from UPS
Event
ID
ID
Definition of Trap
4 of 4
Table 26: UPS Alarms to the Media Server
Event
ID
Alarm
Level
Level
Alarm Text, Cause/Description, Recommendation
1–8
MAJ
“upsEstimatedMinutesRemaining” — UPS does not have an AC-power
source.
source.
1. Restore AC power to the UPS.
12
MAJ
“upsAlarmShutdownPending” — A shutdown-after-delay countdown is
underway (i.e., the UPS has been commanded off).
underway (i.e., the UPS has been commanded off).
1. Stop countdown timer. (Can be done via SNMP messages.)
13
MAJ
“upsAlarmShutdownImminent” — The UPS will turn off power to the load in
< 5 seconds.
< 5 seconds.
1. Restore AC power to the UPS.