LDVR Series Direct Vent Gas Fireplace
10007317
Vertical  Sidewall Installation
STEP 1
Locate vent opening on the wall. It may be necessary 
to first position the fireplace and measure to obtain hole 
location. Depending on whether the wall is combustible 
or noncombustible, cut opening to size. (Fig. 25)
For combustible walls first frame in opening.
Combustible Walls (Fig. 25): Cut a 9³⁄₈”H x 9³⁄₈” W 
(240 x 240mm) hole through the exterior wall and 
frame.
Noncombustible Walls (Fig. 25): Hole opening must 
be 7.5” (190mm) in diameter. 
VO584-100
Vent Opening
2/99   djt
Vent Opening for Combustible Wall
9³⁄₈”
(240mm)
9³⁄₈”
(240mm)
Fireplace Hearth
Framing Detail
Opening for Noncombustible Wall
7¹⁄₂”
(190mm)
VO584-100
Fig. 25  Locate vent opening on wall.
STEP 2
Measure wall thickness and cut adjustable zero 
clearance sleeve parts to proper length (MAXIMUM 
12”/305mm). (Fig. 26) Adjust sleeve to minimum (9³⁄₈” x 
9³⁄₈” and attach to firestop with #8 sheet metal screws 
(supplied). Assemble sleeve and attach to firestop with 
#8 sheet metal screws (supplied). Install firestop as-
sembly.
Zero clearance sleeve is only required for 
combustible walls.
STEP 3
Apply a bead of high temperature sealant to the inner 
and outer flue collars of the fireplace and using ap-
propriate venting component(s) attach to fireplace with 
three (3) screws. (Fig. 27) Follow with the installation 
of the inner and outer elbow. Again secure joints with 
three (3) sheet metal screws. Wipe off any excess high 
temperature sealant.
CFM135 
Zero Clearance Sleeve
2/26/01  sta
Adjustable Zero Clear-
ance Sleeve
Maximum Length 
12” (305mm)
#8 Screws (2)
Adjust-
able Zero 
Clearance 
Sleeve
Firestop
#8 Screws 
(2)
Wall Exterior
Wood Framing
Firestop
Vent Pipe
Drywall
Zero Clearance 
Sleeve Flush with 
Wall Exterior
CFM135
Fig. 26  Locate vent opening on wall.
#8 Screws (2)
STEP 4
Measure the horizontal length requirement including a 
2” (50mm) overlap, i.e. from the elbow to the outside 
wall finish plus 2”, or the distance required if installing a 
second 90° elbow. (Fig. 28)
STEP 5
Use appropriate length of pipe section - telescopic or 
fixed - and install the horizontal vent sections. The 20” 
(508mm) section of pipe which goes through the wall is 
packaged with the 7TDVSK starter kit, and can be cut 
to suit if necessary. (Fig. 29)
Sealing vent pipe and firestop gaps with 
high temperature sealant will restrict cold 
air being drawn in around fireplace.
��������
CFM143
2/2/01    sta
Ensure Pipes are 
Concentric
Bead of Seal-
ant
(If necessary)
CFM143
Fig. 27  Apply sealant to inner and outer pipe.