Under Ceiling Type
Installation Manual
Toshiba
3
SELECTION OF INSTALLATION PLACE
WARNING
• Install the air conditioner at enough strong place 
to withstand the weight of the unit.
If the strength is not enough, the unit may fall down 
resulting in injury.
• Install the air conditioner at a height 8’ (2.4 m) or 
more from the floor.
If you insert your hands or others directly into the unit 
while the air conditioner operates, it is dangerous 
because you may contact with revolving fan or active 
electricity.
CAUTION
• Do not install the air conditioner in a location 
subject to a risk of exposure to a combustible gas.
If a combustible gas leaks and stays around the unit, 
a fire may occur.
Upon approval of the customer, install the air 
conditioner in a place that satisfies the 
following conditions.
• Place where the unit can be installed horizontally.
• Place where a sufficient servicing space can be 
ensured for safety maintenance and check.
• Place where drained water will not cause any 
problem.
Avoid installing in the following places.
• Place exposed to air with high salt content (seaside 
area), or place exposed to large quantities of sulfide 
gas (hot spring). 
(Should the unit be used in these places, special 
protective measures are needed.)
• Place exposed to oil, vapor, oil smoke or corrosive 
gas.
• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place where the discharged air blows directly into 
the window of the neighbor house. (Outdoor unit)
• Place where noise of the outdoor unit is easily 
transmitted.
(When install the outdoor unit on the boundary with 
the neighbor, pay due attention to the level of noise.)
• Place with poor ventilation. (Before air ducting work, 
check whether value of fan speed, static pressure 
and duct resistance are correct.)
„
Installation space
Secure the specified space in the figure for 
installation and servicing.
Unit: in (mm)
„
Height of ceiling
Set the installable height of the ceiling within 13’1” (4 
m), otherwise the air distribution will become poor.
If height of ceiling exceeds 11’6” (3.5 m), hot air 
becomes difficult to reach the floor surface, and then 
the change of setup of high ceiling is necessary.
For the change method of high ceiling, refer to the 
application control, “In case of installation to high 
ceiling” and “In case of incorporating filter sold 
separately” in this Manual.
List of installable ceiling height
According to the conditions of installation, setup time of 
turning-on of filter sign (notification of filter cleaning) of 
the remote control can be changed.
When it is difficult to warm up the room due to 
installation place or structure of the room, the detection 
temperature of heating can be raised.
For change the setup time, refer to the application 
control, “Change of filter sign turning-on time” and 
“How to increase the heating effect” in this Manual.
Setup data
0000
Standard 
(Factory default)
11’6” (3.5 m) or less
0001
High ceiling 1
more than 11’6” (3.5 m) 
up to 13’1” (4.0 m)
9.8” (250) 
or more
19.7”
 (500)
 or
 more
9.8” (250) 
or more