Manual 2100-467K 
Page 
14 of 24
table  6
thermOstat WIre sIze
transFOrmer taPs
230/208V, 1 phase and 3 phase equipment employ dual 
primary voltage transformers.  All equipment leaves 
the factory wired on 240V tap.  For 208V operation, 
reconnect from 240V to 208V tap.  The acceptable 
operating voltage range for the 240 and 208V taps are:
 
taP  
ranGe
 
 240 
253 – 216
 
 208 
220 – 187
NOTE:  The voltage should be measured at the field 
power connection point in the unit and while 
the unit is operating at full load (maximum 
amperage operating condition).
WIrInG  –  maIn POWer
Refer to the unit rating plate for wire sizing information 
and maximum fuse size.  Each outdoor unit is marked 
with a “Minimum Circuit Ampacity”.  This means that 
the field wiring used must be sized to carry that amount 
of current.  If field installed heaters are added to the 
basic unit, a second separate power supply circuit will 
be required.  The heater rating plate located adjacent 
to the basic unit rating plate will show the appropriate 
circuit ampacity fuse size, etc.  (Also see “Electrical 
Specifications” on pages 5 & 7.)  All models are 
suitable for connection with copper wire only.  
These 
instructions must be adhered to.  Refer to the National 
Electrical Code for complete current carrying capacity 
data on the various insulation grades of wiring material.  
The electrical specifications list fuse and wire sizes 
(75°F copper) for all models including the most 
commonly used heater sizes.
The unit rating plate lists a “Maximum Time Delay 
Fuse” or “HACR” type circuit breaker that is to be used 
with the equipment.  The correct size must be used for 
proper circuit protection and also to assure that there 
will be no nuisance tripping due to the momentary high 
starting current of the compressor.
WIrInG – 24V lOW VOltaGe cOntrOl 
cIrcuIt
Five (5) wires should be run from thermostat subbase 
to the 24V terminal board in the unit.  A five conductor, 
18 gauge copper, color-coded thermostat cable is 
recommended.  The connection points are shown in 
Figure 6.
thermOstats
See specific wiring information for the different models, heater KWs, and voltages on unit and heating wiring 
diagrams.
IMPORTANT NOTE:  Only the thermostats as shown above will work with this equipment.  The thermostats and    
 
correct operation can be assured only by proper selection and application of these parts.
table 7
Wall thermOstats
transformer
Va
Fla
Wire
Gauge
maximum
Distance  
In Feet
55
2.3
20
18
16
14
12
45
60
100 
160
250
thermostat
Predominant Features
8403-058
(TH5220D1151)
2 stage Cool;  2 stage Heat
Electronic Non-Programmable
Auto or Manual changeover
8403-060
(1120-445)
3 stage Cool;  3 stage Heat
Programmable/Non-Programmable Electronic
HP or Conventional
Auto or Manual changeover