Справочник Пользователя для Bard PA13422-C

Скачать
Страница из 24
Manual 2100-467K 
Page 
16 of 24
start uP
These units require R-410A refrigerant and Polyol Ester 
oil.
General:
1.  Use separate service equipment to avoid cross    
 
contamination of oil and refrigerants.
2.  Use recovery equipment rated for R-410A  
 
 refrigerant.
3.  Use manifold gauges rated for R-410A (800  
 
 
psi/250 psi low).
4.  R-410A is a binary blend of HFC-32 and HFC-125.
5.  R-410A is nearly azeotropic - similar to R-22 and  
 
R-12.  Although nearly azeotropic, charge with   
 
liquid refrigerant.
6.  R-410A operates at 40-70% higher pressure than   
 
R-22, and systems designed for R-22 cannot  
 
 
withstand this higher pressure.
7.  R-410A has an ozone depletion potential of zero,  
 
but must be reclaimed due to its global warming  
 potential.
8.  R-410A compressors use Polyol Ester oil.
9.  Polyol Ester oil is hygroscopic; it will rapidly    
 
absorb moisture and strongly hold this moisture in  
 
the oil.
10. A liquid line dryer must be used - even a deep    
 
vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug  
 
compressor immediately after removal.  Purge with  
 
small amount of nitrogen when inserting plugs.
tOPPInG OFF sYstem charGe
If a leak has occurred in the system, Bard 
Manufacturing recommends reclaiming, evacuating 
(see criteria above), and charging to the nameplate 
charge.  Topping off the system charge can be done 
without problems.
With R-410A, there are no significant changes in the 
refrigerant composition during multiple leaks and 
recharges.  R-410A refrigerant is close to being an 
azeotropic blend (it behaves like a pure compound 
or single component refrigerant).  The remaining 
refrigerant charge, in the system, may be used after 
leaks have occurred and then “top-off” the charge by 
utilizing the pressure charts on the inner control panel 
cover as a guideline.
REMEMBER:  When adding R-410A refrigerant, 
it must come out of the charging cylinder/tank as a 
liquid to avoid any fractionation, and to insure optimal 
system performance.  Refer to instructions for the 
cylinder that is being utilized for proper method of 
liquid extraction.
saFetY PractIces:
1.  Never mix R-410A with other refrigerants.
2.  Use gloves and safety glasses, Polyol Ester oils can  
 
be irritating to the skin, and liquid refrigerant will  
 
freeze the skin.
3.  Never use air and R-410A to leak check; the  
 
 
mixture may become flammable.
4.  Do not inhale R-410A – the vapor attacks the    
 
nervous system, creating dizziness, loss of  
 
 
coordination and slurred speech.  Cardiac  
 
 
irregularities, unconsciousness and ultimate death  
 
can result from breathing this concentration.
5.  Do not burn R-410A.  This decomposition  
 
 
produces hazardous vapors.  Evacuate the area if  
 exposed.
6.  Use only cylinders rated DOT4BA/4BW 400.
7.  Never fill cylinders over 80% of total capacity.
8.  Store cylinders in a cool area, out of direct  
 
 sunlight.
9.  Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge  
 
lines or cylinders.  R-410A expands significantly  
 
at warmer temperatures.  Once a cylinder or line is  
 
full of liquid, any further rise in temperature will  
 
cause it to burst.
start uP nOtes
For improved start up performance, wash the indoor 
coil with dishwasher detergent.