Справочник Пользователя для Bard PA13422-C

Скачать
Страница из 24
Manual 2100-467K 
Page 
20 of 24
(c
ontinued on Page 20 in 
table 1
1)
table
  9
Pressure
 t
able
c
OO
lI
n
G
Air 
Temperature Entering Outdoor Coil Degree F
LOW
 SIDE
 PRESSURE
 +4 PSIG
HIGH S
IDE
 P
RESSURE
 +10 
PSIG
Tables
based
upon
rated
CFM
(airflow)
across
the
evaporator
coil.
If incorrect charge suspected (more than 
+4
psig
suction,
+
10
psig
liquid),
it
is
recommended
refrigerant
charge
be
reclaimed,
system
evacuated
and
charged
to
serial
plate
quantity
.
Model
Return Air  Temperature
Pressure
65°
70°
75°
80°
85°
90°
95°
100°
105°
110°
115°
120°
125°
PA1324
75° DB 62° WB
Low Side High Side
125 238
127 262
129 286
131 310
133 334
135 358
137 382
138 407
140 432
142 457
143 482
145 507
147 532
80° DB 67° WB
Low Side High Side
134 244
136 269
138 293
140 318
142 343
144 367
146 392
148 418
150 443
151 469
153 494
155 520
157 546
85° DB 72° WB
Low Side High Side
144 253
146 278
148 304
151 329
153 355
155 380
157 406
159 432
161 459
163 485
165 512
167 538
169 565
PA1330
75° DB 62° WB
Low Side High Side
126 246
128 267
131 289
133 310
135 332
137 353
139 374
141 402
143 429
145 457
148 484
150 512
152 539
80° DB 67° WB
Low Side High Side
135 252
137 274
140 296
142 318
144 340
147 362
149 400
151 412
153 440
156 469
158 497
160 525
162 553
85° DB 72° WB
Low Side High Side
145 261
148 284
150 306
153 329
155 352
158 375
160 397
163 427
165 456
167 485
170 514
172 543
174 573
PA1336
75° DB 62° WB
Low Side High Side
125 247
127 271
128 295
130 320
132 344
133 369
135 393
136 418
138 443
139 468
141 494
142 519
80° DB 67° WB
Low Side High Side
134 253
136 278
137 303
139 328
141 353
142 378
144 413
146 429
147 455
149 480
150 506
152 532
85° DB 72° WB
Low Side High Side
144 262
146 288
148 314
149 339
151 365
153 391
155 417
157 444
158 471
160 497
162 524
163 551