electrIcal data
General
Check  the  boiler  model  and  rating  plate  information  against  the 
characteristics of the branch circuit electrical supply. Do not connect 
the boiler to an improper source of electricity.  
Voltage applied to the boiler  should not vary more than + 5% to -10% 
of the model and rating plate marking for satisfactory operation.
Do not energize the branch circuit for any reason before the boiler is 
filled with water. Doing so may cause the heating elements to burn 
out. Such damage is not covered under the terms of the warranty.
The  branch  circuit  is  connected  to  the  block  through  an  opening 
provided on top of the boiler.
The  boiler  should  be  connected  to  a  separate,  grounded,  branch 
circuit with overcurrent protection and disconnect switch. These are 
part  of  the  electrical  supply  system  not  components  of  the  boiler, 
as such they are obtained locally. The boiler should be grounded in 
accordance with national and local codes.
Branch cIrcuIt
The branch circuit wire size should be established through reference 
to the National Electrical Code or other locally approved source in 
conjunction with boiler amperage rating. Branch circuit wiring which 
connects  to  the  boiler  terminal  block  should  be  temperature  rated 
at 75°C. For convenience, portions of the wire size tables from the 
Code are reproduced here. It is suggested the electrician size the 
branch circuit at 125 percent of the boiler rating and further increase 
wire size as necessary to compensate for voltage drop in long runs. 
Branch circuit voltage drop should not exceed 3% at the boiler.
calculatInG aMperaGe/ 
oVercurrent protectIon
The boiler is factory wired for connection to three wire single-phase 
or  three  and  four  wire  three-phase  branch  circuits.  In  addition,  a 
ground conductor may be required.
A diagram of the wiring “as built” is furnished with the boiler for the 
electrician’s use. An amperage table is on pages 7 & 12 of this manual. 
The boiler model and rating plate provides full load amperage data. 
Typical or Standard wiring diagrams are provided on pages 13 & 14 
of this manual.
The rating of the overcurrent protection should be computed on the 
basis of 125 percent of the total connected load amperage.   Where the 
standard ratings and settings do not correspond with this computation, 
the next higher standard rating or setting should be selected.
BoIler cIrcuIts
The  boiler’s  electrical  components  are  pictured  and  identified  on 
page 8. The model and rating plate illustration on page 9 identifies the 
electrical characteristics. Basically, there are two electrical circuits:
•  The  control  circuit,  where  the  temperature  control  directly  or 
indirectly operates the contactor coils.
•  The power circuit, which is operated by the control circuit, carries 
the electrical load of the heating elements.
The following describes the circuits and includes typical wiring diagrams. 
All circuits are designed for 60 or 50 Hertz alternating current.
Refer to ELECTRICAL CONFIGURATION TABLE, below, and wiring 
diagram provided with your boiler before completing connections to 
electrical supply.
NOTE:  Wiring  diagrams  in  this  manual  are  typical  examples.  The 
specific wiring diagram “as built” for your boiler is typically attached to 
the “inner side” of the control panel. 
control cIrcuIt
All control circuits are operated on single-phase 120V. A transformer 
is used in the control circuit. 
Control  circuit  wiring  is  14 Awg,  THHN  or  THWN  type,  rated  600 
volts, 105°C.
Seperate instructional literature is provided with the boiler for step control.
portion of table 310-16
Allowable Ampacities of Insulated 
Copper Conductors
Not more than three conductors in 
raceway or cable or direct burial 
(based on ambient temperature of 
30°C, 86°F.)
portion of table 310-16
Allowable Ampacities of Insulated 
Aluminum and Copper-Clad 
Aluminum Conductors
Not more than three conductors in 
raceway or cable or direct burial 
(based on ambient temperature of 
30°C, 86°F.)
size
temperature 
rating of 
conductor. see 
table 310-13 in 
code
size
temperature 
rating of 
conductor. see 
table 310-13 in 
code
awG
McM
75°c (167°f) 
types rh, 
rhw, ruh (14-
2), thw, thwn, 
Xhhw, use
awG
McM
75°c (167°f) 
types rh, 
rhw, ruh (12-
2), thw, thwn, 
Xhhw, use
18
16
14
12
10
8
- - - - -
- - - - -
15
20
30
45
12
10
8
6
4
3
15
25
40
50
65
75
6
4
3
2
1
1/0
65
85
100
115
130
150
2
1
1/0
2/0
3/0
4/0
90
100
120
135
155
180
2/0
3/0
4/0
250
300
350
175
200
230
255
285
310
250
300
350
400
500
600
205
230
250
270
310
340
400
500
600
700
750
800
900
335
380
420
460
475
490
520
700
750
800
900
1000
1250
1500
375
385
395
425
445
485
520
1000
1250
1500
1750
2000
545
590
625
650
665
1750
2000
545
560
These capacites relate only to conductors 
described in Table 310-13 in Code.
For ambient temperatures over 30°C, see 
Correction Factors, Note 13 in Code