S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
21
65-0303—05
Fig. 37. System identification and access configuration. 
(Hydronic Screen Shown.)
Table 6 displays System Identification and Access parameters.
When the burner name is changed, the name is saved in the 
R7910A or R7911 and displayed in the title of all pages that 
zoom into the control.
Default parameter settings for installer and Honeywell 
passwords are “sola” and “solaoem,” respectively. These 
passwords most likely have been changed by Honeywell.
Factory Data gives Honeywell an option to display a brand 
name other than Sola on this configuration page. Additional 
information displayed on this page is listed in Table 7.
Central Heat Parameters 
(R7910A Hydronic Control Only)
Table 8 displays Central Heat Hydronic Control configuration 
parameters.
Fig. 38. Central Heat hydronic configuration.
Table 6. System Identification and Access Parameters.
Parameter
Comment
Boiler Name
Name to identify boiler (up to 20 
characters)
Installation
Notes regarding installation (up to 20 
characters)
Installer password
Change installer password setting
OEM password
Change OEM password setting
Factory Data
OEM name to associate with boiler 
(up to 20 characters)
Table 7. System Identification Information.
Status
Comment
Product Type
Type of product that the burner is
OS Number
Model number associated with burner
Software Version
Version of software running in the 
R7910A or R7911
Date Code
Date when R7910A or R7911 was 
assembled
Application Revision Version of application data in the 
R7910A or R7911
Safety Revision
Revision of safety data in the R7910A 
or R7911
Table 8. Central Heat Hydronic 
Configuration Parameters.
Parameter
Comment
CH enable
Disable or Enable Central Heating 
Loop
Demand switch
Sensor for Central Heat demand:
Sensor only
Sensor & STAT terminal
Sensor & Remote Stat
LCI & Sensor
Outdoor reset
Enabled
Disabled
CH has priority over 
Lead Lag
Yes, No, Cancel
Setpoint source
Local
S2 (J8-6) 4-20mA
Setpoint
Setpoint for normal Central Heat 
modulation:
-40 °F to 266 °F (-40 °C to 130 °C)
Time of day setpoint Setpoint when Time Of Day switch is 
on. -40 °F to 266 °F (-40 °C to 130 °C)
Off hysteresis
Differential above setpoint when boiler 
is turned off.
32 °F to 266 °F (0 °C to 130 °C)
On hysteresis
Differential from setpoint when boiler 
is turned on. 32 °F to 266 °F (0 °C to 
130 °C)
4 mA water 
temperature
-40 °F to 266 °F (-40 °C to 130 °C)
20 mA water 
temperature
-40 °F to 266 °F (-40 °C to 130 °C)
Modulation sensor
Outlet sensor, Inlet sensor, S5 (J8-11)