S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
23
65-0303—05
Domestic Hot Water (DHW) 
Configuration Parameters 
(R7910A Hydronic Control Only)
Table 11 displays Domestic Hot Water (DHW) configuration 
parameters.
Fig. 41. Domestic Hot Water (DHW) configuration.
DHW Storage Configuration
Table 12 displays DHW Storage configuration parameters.
DHW Plate Heat Exchanger 
Configuration
Table 13 displays DHW Plate Heat Exchanger configuration 
parameters.
Table 11. Domestic Hot Water (DHW)
Configuration Parameters.
Parameter
Comment
Enable
Disable or Enable Domestic Hot 
Water Loop
Demand switch
Sensor for Central Heat demand:
DHW sensor only,
DHW sensor & Remote Stat,
DHW switch & inlet sensor, or
DHW switch & outlet sensor
Priority source
Which system has priority:
Disabled or
Heat Demand
Priority method
Boost during priority time
Drop after priority time
Modulation sensor
DHW Sensor
Outlet Sensor
Inlet Sensor
Auto: DHW (S6) or Inlet Sensor
Auto: DHW (S6) or Outlet Sensor
Setpoint 
-40 °F to 240 °F (-40 °C to 115 °C)
Time of day setpoint Setpoint when Time Of Day switch is 
on. -40 °F to 240 °F (-40 °C to 115 °C)
Off hysteresis
Differential above setpoint when boiler 
is turned off. -40 °F to 240 °F (-40 °C 
to 115 °C)
On hysteresis
Differential from setpoint when boiler 
is turned on. 
2 °F to 234 °F (-16 °C to 112 °C)
DHW priority 
override time
___hour ___min ___sec
Hysteresis step 
time
___hour ___min ___sec
DHW priority vs CH Which system has priority:
Central Heat over Domestic Hot 
Water, or 
Domestic Hot Water over Central Heat
DHW priority vs 
Lead Lag
Which system has priority:
Lead Lag over Domestic Hot Water,
Domestic Hot Water over Lead Lag
DHW P-gain
Gain applied for the P portion of the 
PID equation
0-400
DHW I-gain
Gain applied for the I portion of the 
PID equation
0-400
DHW D-gain
Gain applied for the D portion of the 
PID equation
0-400
Table 12. DHW Storage Configuration Parameters.
Parameter
Comment
DHW storage 
enable
Enabled, Disabled
Storage time
___hour ___min ___sec
Setpoint
-40 °F to 266 °F (-40 °C to 130 °C)
Off hysteresis
-0 °F to 180 °F (-17 °C to 82 °C)
On hysteresis
-0 °F to 180 °F (-17 °C to 82 °C)
Table 13. DHW Plate Heat Exchanger 
Configuration Parameters.
Parameter
Comment
Tap detect degrees -0 °F to 180 °F (-17 °C to 82 °C)
Tap detect on 
recognition time
___hour ___min ___sec
Tap detect on 
threshold
-0 °F to 180 °F (-17 °C to 82 °C)
Tap detect minimum 
on time
___hour ___min ___sec
Tap stop inlet-DHW 
degrees
-0 °F to 180 °F (-17 °C to 82 °C)
Tap stop outlet-Inlet 
degrees
-0 °F to 180 °F (-17 °C to 82 °C)
Table 11. Domestic Hot Water (DHW)
Configuration Parameters. (Continued)
Parameter
Comment