The following features are available in Access Level 2: 
 
3.1 
The SILENCE RESOUND ALARMS button is used to silence or re-sound the alarms as 
required.  Repeated pressing toggles between the two.  In addition to silencing the 
sounders in the event of an alarm, this can be used to test the sounder circuits or evacuate 
the building as required. 
 
3.2 
The RESET button is used to reset the panel.  If any fault and/or alarm conditions still 
exist, they will be displayed in the usual way and they will need to be cleared before the 
panel can be reset. 
 
3.3 
The SILENCE BUZZER button is used to silence the panel’s internal buzzer. 
 
3.4 
The SCROLL button allows multiple messages (as indicated via the MORE MESSAGES 
light) to be viewed in the LCD display. 
 
3.5 
The MENU button gives access to additional features via the LCD display (the Access 
Level 2 menu structure is summarised below).  After pressing the MENU button, press 
button 1 (“USER FUNCTION”) and then use the UP or  DOWN keys to select: 
 
 
TIME/DATE 
Used to set the time and date. 
 
VIEW 
This shows the total number of alarms registered by the panel since 
commissioning. 
 
DISABLEMENTS 
This allows for a zone and/or the auxiliary alarm output (if installed) 
and/or the auxiliary fire output (if installed) to be disabled / re-
enabled as required.  Enter the sub-menu using SEL (4) and then 
UP or DOWN to reach ZONE DISABLEMENT, ALM DISABLEMENT 
or FIRE DISABLEMENT as required.  Pressing TOG (2) toggles 
between enable and disable for each feature.  To set a condition 
once selected, press ENTER.  The GENERAL DISABLE light will be 
lit and, if a zone has been disabled, the relevant yellow zone light 
will also be lit. 
 
DAY/NIGHT MODE  This enables / disables the Day/Night mode.  In this mode, when an 
alarm condition occurs, the panel’s internal buzzer will sound, but 
the alarms will not sound for a pre-set period (programmed during 
commissioning).  This allows time to determine the cause of the 
alarm before initiating an evacuation.  To programme or change the 
delay period, contact your service provider. 
 
MENU
1: USER FUNCTION
TIME/DATE
*ENTER NEW DATE*
DD/MM/YYYY
VIEW
ALARM COUNTER
*ALARM COUNTER*
TOTAL ALARMS     0
DISABLEMENTS
ZONE DISABLEMENT
ZONE 1 ENABLED
ALM DISABLEMENT
AUX ALARMS EN
FIRE DISABLEMENT
AUX FIRE EN
DAY/NIGHT MODE
2: ENT ENG CODE
*ENGINEER CODE*
7134 (DEFAULT)