4. 
WHEN AN ALARM CONDITION OCCURS 
 
When a fire condition is detected in a zone, the relevant red zone alarm light flashes, the red ALARM 
light flashes, the alarm sounder circuits are activated (unless programmed off or delayed via 
DAY/NIGHT mode) and the buzzer on the panel sounds.  The LCD display will show ZONE(number) 
FIRE followed by the time at which the alarm was activated.   
 
After the appropriate fire drill has been completed, to switch off the buzzer, enter Access Level 2 and 
press the SILENCE BUZZER button.  The buzzer stops, the zone light and the ALARM light continue 
flashing and the audible alarm circuits continue to sound (unless programmed off).  When the fire 
condition has been rectified, to reset the system: 
 
 
In Access Level 2, press the SILENCE ALARMS button.  The audible alarms stop, but the red 
zone alarm light and the ALARM light stay on.  If another zone alarm condition occurs, the new 
red zone alarm light and the ALARM light will flash, the buzzer will sound and, unless 
programmed off, audible alarms will sound and the original red zone alarm light will stay on. 
 
Note: It is not possible to reset the panel until the SILENCE ALARMS button has been 
pressed. 
 
 
When all zone fire conditions have been rectified, press the RESET button. 
 
If the fire condition still exists, the panel will revert to the alarm condition.  To reset the panel it may be 
necessary to clear smoke or heat from the detectors and to replace the glass in the manual fire call 
point. 
 
5. 
WHEN A FAULT CONDITION OCCURS 
 
If a fault occurs in one or more zones, the relevant yellow zone fault light flashes, the yellow 
GENERAL FAULT light flashes and the buzzer on the panel sounds intermittently. If a fault in the 
Sirius 
II
 panel (system fault) occurs, the yellow SYSTEM FAULT light flashes, the yellow GENERAL 
FAULT light flashes and the buzzer on the panel sounds intermittently.  If a zone and/or system fault 
is indicated: 
 
 
Enter Access Level 2. 
 
Press the SILENCE BUZZER button (the buzzer stops, the yellow GENERAL FAULT and/or 
SYSTEM FAULT lights continue flashing).  The buzzer will automatically re-sound if any more 
fault or alarm conditions occur 
 
Contact your authorised service provider to rectify the fault 
 
When the fault has been rectified, reset the panel by pressing RESET
 
 
6. 
CARE AND MAINTENANCE 
 
Repair and routine maintenance of Sirius 
II
 should only be carried out by suitably qualified service 
personnel in accordance with all applicable local and national regulations, standards and working 
practices.  However, the user should: 
 
 
Ensure that all performance checks and maintenance operations carried out on the fire alarm 
system are recorded in the Maintenance Record (page 4). 
 
 
Examine the exterior of the panel and enclosure regularly for damage or loose cable glands and 
report any faults to their service provider. 
 
 
On a regular basis or as directed by their service provider, carry out a panel lights and buzzer 
test.  Notify any defects to their service provider.