9.  All vent (exhaust) pipes must be pitched a minimum of a 1/4 
inch per foot back to the water heater (to allow drainage of 
condensate).
10. if  installing  3  inch  vent  pipe  connect  the  vent  pipe  to  the 
exhaust elbow on the water heater.
11. if installing 4 inch pipe transition to 3 inch pipe at the exhaust 
elbow on the water heater as shown in Figure 18. The field 
installed  3”  pipe  between  the  exhaust  elbow  and  the  4”  x 
3” reducer coupling should be 18 inches (45 cm) or less in 
length.
direct Vent installation
Venting requirements on page 24 before proceeding. These 
instructions and requirements  must be followed  in addition 
to  the  instructions  below  that  are  specific  for  Direct  Vent 
configurations.
2.  Determine  which  Direct  Vent  arrangement  will  be  used  for 
the  installation.  There  are  six  (6)  Direct  Vent  arrangement 
3.  Determine vent and intake air pipe size to be used for the 
4.  Plan the layout of the vent and intake air piping backwards 
from  the  termination  point  outdoors  to  the  water  heater. 
Layout the vent and intake air piping to use a minimum of 
pipe and elbows.
5.  install the terminations first. 
if  standard  terminations  are  being  used  and  the  intake  air 
or  vent  piping  will  terminate  vertically,  through  a  roof,  see 
Vertical Termination installation on page 27. 
if standard terminations are being used and the intake air or 
vent piping will terminate horizontally, through a sidewall, see 
Sidewall Termination installation on page 29. 
if  a  concentric  termination(s)  will  be  used  see  Concentric 
6.  When  installation  of  the  termination(s)  is  complete  install 
necessary piping and fittings to route the intake air and vent 
piping back to the water heater.
7.  The intake air and vent piping must be supported properly 
to avoid bending or failure. The water heater manufacturer 
recommends that the vent and intake air piping be supported 
every 5 feet (152 cm) of vertical run and every 3 feet (91 cm) 
of horizontal run.
8.  Do not install the vent or intake air piping in a manner that will 
allow water to be trapped in the piping.
9.  A field supplied condensate Tee fitting and drain hose should 
be installed in the intake air piping near the water heater in 
colder climates with heavy snow accumulations and in areas 
that  regularly  experience  high  humidity.  The  drain  hose 
should be routed to an adequate floor drain separate from 
any other condensate drains. See Figure 21 on page 26.
note: Snow being pulled into the intake air piping and then 
melting can lead to excessive amounts of water accumulation 
and damage water heater components. Warm, humid outdoor 
air can lead to excessive condensation inside the intake air 
piping and may also damage water heater components.
10. The intake air and vent (exhaust) piping must be pitched a 
minimum of a 1/4 inch per foot back to the water heater (to 
allow drainage of condensate).
Venting installation seQuence
Venting requirements on page 24 before proceeding. These 
instructions  and  requirements  must  be  followed  on  all 
installations.
2.  Determine  whether  the  water  heater  will  be  installed  in 
a  Power  Vent  or  Direct  Vent  configuration  and  which  vent 
system arrangement will be used for the installation. See the 
3.  Proceed to the applicable instructions:
power Vent installation
Venting requirements on page 24 before proceeding. These 
instructions and requirements  must be followed  in addition 
to  the  instructions  below  that  are  specific  for  Power  Vent 
configurations.
2.  Determine which Power Vent arrangement will be used for 
the installation; vertical or horizontal termination. See Figure 
3.  Determine the vent pipe size for the installation, see Venting 
4.  Plan  the  layout  of  the  vent  piping  backwards  from  the 
termination  point  outdoors  to  the  water  heater.  Layout  the 
vent piping to use a minimum of pipe and elbows.
5.  install the termination first.
if the vent piping will terminate vertically, through a roof, see 
Vertical Termination installation on page 27. 
if  the  vent  piping  will  terminate  horizontally,  through  a 
6.  When  installation  of  the  termination  is  complete  install 
necessary piping and fittings to route the vent piping back to 
the water heater.
7.  The vent pipe must be supported properly to avoid bending 
or failure. The water heater manufacturer recommends that 
the vent pipe be supported every 5 feet (152 cm) of vertical 
run and every 3 feet (91 cm) of horizontal run.
8.  Do not install the vent piping in a manner that will allow water 
to be trapped in the piping.
3” PIPE FIELD
SUPPLIED
EXHAUST ELBOW
VENT CONNECTION
FACTORY INSTALLED
4” PIPE FIELD
SUPPLIED
4” x 3” REDUCER
FIELD SUPPLIED
VENT (EXHAUST) CONNECTION
figure 18