hIGh altItude InstallatIons
This  high  efficiency  water  heater  is  certified  for  use  without 
modification for an altitude of 10,000 feet (3,079 meters). Consult 
the factory for installation at altitudes over 10,100 feet (3,079m).
Some  gas  utility  companies  derate  their  gas  for  altitude,  making 
it unnecessary to install high altitude orifices. Call the local gas or 
utility company to verify BTU content.
Due to the input ration reduction at high altitudes, the output rating 
of the appliance is also reduced and should be compensated for in 
the sizing of the equipment for applications.
Use pipe joint compound or teflon tape marked as being resistant 
to the action of petroleum [Propane (L.P.)] gases. 
The appliance and its gas connection must be leak tested before 
placing the appliance in operation.
The appliance and its individual Shut-off valve shall be disconnected 
from the gas supply piping system during any pressure testing of 
that system at test pressures in excess of 1/2 pound per square 
inch (3.5 kPa). It shall be isolated from the gas supply piping system 
by closing its individual manual Shut-off valve during any pressure 
testing of the gas supply piping system at test pressures equal to 
or less than 1/2 pound per square inch (3.5 kPa).
IMPORTANT:  MAKE  SURE  THE  GAS  LINE  IS  PIPED  IN  WITH 
HARD PIPE. AvOID FLEX LINE CONSTRUCTION FOR GAS DUE 
TO POSSIBLE GAS FLOW PROBLEMS.
sedIMent traps
A sediment trap shall be installed as close to the gas inlet of the 
water heater as practical at the time of water heater installation. 
The sediment trap shall be either a tee fitting with a capped nipple 
in  the  bottom  outlet  or  other  device  recognized  as  an  effective 
sediment trap. 
Contaminants  in  the  gas  lines  may  cause  improper  operation  of 
the gas control valve that may result in fire or explosion. Before 
attaching  the  gas  line  be  sure  that  all  gas  pipe  is  clean  on  the 
inside. To trap any dirt or foreign material in the gas supply line, a 
drip leg (sometimes called a sediment trap) must be incorporated 
in  the  piping.  The  drip  leg  must  be  readily  accessible.  Install  in 
accordance  with  the  “Gas  Piping”  section.  Refer  to  the  current 
edition of the National Fuel Gas Code (ANSI Z223.1/NFPA 54).
fIllInG the water heater
Never use this water heater unless it is completely full of water. 
To prevent damage to the tank, the tank must be filled with water. 
Water must flow from the hot water faucet before turning “ON” gas 
to the water heater.
To fill the water heater with water:
1.  Close the water heater drain valve by turning the handle to the 
right (clockwise). The drain valve is on the lower front of the 
water heater.
2.  Open  the  cold  water  supply  valve  to  the  water  heater.  
 
note: the cold water supply valve must be left open when 
the water heater is in use.
3.  To insure complete filling of the tank, allow air to exit by opening 
the nearest hot water faucet.  Allow water to run until a constant 
flow is obtained. This will let air out of the water heater and the 
piping.
4.  Check  all  water  piping  and  connections  for  leaks.  Repair  as 
needed.