INSTALLATION – SOLAR STORAGE TANK 
 
THIS WATER HEATER IS FOR OUTDOOR INSTALLATION ONLY. 
THIS WATER HEATER IS NOT SUITABLE FOR POOL HEATING. 
Check the water heater is suitable for the gas type available. 
(refer to the rating label on the water heater) 
 
The system is suitable for installation with Solahart ‘J’ or ‘KF’ solar collectors. 
 
The solar circuit must be installed with a continuous fall of a minimum 5° in the pipe work from the solar 
collectors to the solar storage tank, the solar hot and solar cold pipes must be fully insulated with closed 
cell polymer insulation (minimum thickness 13 mm) and the system charged with correctly mixed closed 
circuit fluid to offer protection against freeze damage. The system has NO WARRANTY for freeze 
damage if there is not a continuous fall in the solar hot and solar cold pipes or they are uninsulated or 
the closed circuit fluid has been incorrectly mixed (refer to 
 
SOLAR WATER HEATER STORAGE TANK LOCATION 
The solar storage tank is suitable for outdoor installation only. The solar storage tank should be 
installed close to the most frequently used outlet and its position chosen with safety and service in 
mind. Make sure people (particularly children) will not touch the flue terminal. The flue terminal and air 
inlet must be clear of obstructions and shrubbery. 
 
Consideration must also be given to the position of the solar storage tank in relation to the solar 
collectors. There are limitations on both the maximum length of the solar hot and solar cold pipes and 
the maximum height between the solar storage tank and the solar collectors. Refer to 
 
Clearance must be allowed for servicing of the solar 
storage tank and gas booster. The solar storage tank 
must be accessible without the use of a ladder or 
scaffold. Make sure the temperature pressure relief 
valve lever is accessible and the front panel and front 
covers can be removed for service. 
 
You must be able to read the information on the rating 
plate. If possible leave headroom of one water heater 
length so the anode can be inspected or replaced. 
Remember you may have to remove the entire solar 
storage tank later for servicing. 
 
The installation must comply with these installation 
instructions and with the requirements of 
AS/NZS 3500.4, AS 5601, AS/NZS 3000 and all local 
codes and regulatory authority requirements. In New 
Zealand, the installation must conform with the New 
Zealand Building Code. 
 
The water heater must not be installed in an area with a corrosive atmosphere where chemicals are 
stored or where aerosol propellants are released. Remember the air may be safe to breathe, but when 
it goes through a flame, chemical changes take place which may attack the water heater. 
 
It is recommended the solar storage tank be installed at ground or floor level and must stand vertically 
upright. 
 
Note: It is important for the solar storage tank to be orientated vertically upright in order for the falling 
film of closed circuit fluid to operate efficiently. 
 
A secondary flue is not required. The water heater must not be installed indoors or in a confined space.