INSTALLATION – SOLAR STORAGE TANK 
19 
MAINS WATER SUPPLY 
Where the mains water supply pressure exceeds that shown in the table below, an approved pressure 
limiting valve is required and should be fitted as shown in the installation diagram 
 
Model 270 
Relief valve setting 
1000 kPa 
Expansion control valve setting * 
850 kPa 
Max. mains supply pressure 
 
With expansion control valve 
680 kPa 
Without expansion control valve 
800 kPa 
Min. mains supply pressure 
140 kPa 
 
* Expansion control valve not supplied with the water heater. 
 
 
TANK WATER SUPPLY 
If the water heater is supplied with water from a tank supply, then a pressure pump system is 
recommended to ensure a minimum water pressure of 140 kPa is achieved to allow the gas booster to 
operate. Take care to avoid air locks. 
 
Notes: 
•  It is not recommended to install this water heater with a low pressure water supply. 
•  This water heater is not suitable for connection to bore water or spring water unless a water 
treatment device is fitted. 
•  If sludge or foreign matter is present in the water supply, it is recommended a suitable filter be 
incorporated in the cold water line to the water heater. 
• Refer 
to 
“Water Supplies”
 on page 52.