Справочник Пользователя для Rheem Gas Heavy Duty Water Heater Models 265 Litre and 275 Litre

Скачать
Страница из 48
CONNECTIONS – ELECTRICAL 
30 
POWER FLUE EXTERNAL CONTROLS – INTERMITTENT OPERATION 
 
 
 
 
 
INTERLOCK TERMINAL
621 SERIES RHEEM
 
 
 
multiple water heater installation 
Notes 
1.  Power source for the water heater, fan and 
control circuit must be from the same circuit. 
2.  R1 monitors return signal. 
3.  R2 monitors alarm signal. 
4.  T1 to be set for 20-30 seconds. 
5. Meets  requirements  of Clause H.2.2.6 of 
AS5601 – 2004, providing lockout in the event of 
flue product flow failure. 
6.  Where intermittent fan operation is utilised, it is 
necessary to run the fan for some time after 
combustion ceases to prevent flue spillage of 
combustion products. T2 to be set for 5 minutes. 
jumper lead must be removed 
for connection to a power flue 
For a single water heater 
installation, connect 1 and 2 
directly to the water heater
2
2
1
1
1