MULTIPLE INSTALLATIONS 
 
A multiple installation of Rheem water heaters on a single manifold or multiple 
manifolds is possible, using the Rheem Equa-Flow
®
 manifold system, where 
large volumes of hot water are required. The Equa-Flow principle will function 
with water heaters in line, around a corner or in rows back to back 
diagrams on page 
33
)
 
The cold water and hot water manifolds must be designed to balance the flow 
from each water heater. To achieve this, there are basic installation 
requirements and principles which must be followed: 
1.  The maximum number of water heaters in a bank should be 8, however 
several banks of water heaters can be installed. 
2.  The hot water line from the manifold must leave from the opposite end to 
which the cold water line enters the manifold. 
3.  The water heaters must be of the same model. 
4.  The cold water line, cold and hot headers and hot water line must be sized 
to meet the requirements of both AS/NZS 3500.4 and the application. 
5.  A non return valve, isolation valve and if required a pressure limiting valve 
and expansion control valve, must be installed on the cold water line to the 
system. 
heater installation) must be installed on both the cold water branch and hot 
water branch of each water heater. 
7.  Non return valves or pressure limiting valves must not be installed on the 
branch lines to the water heaters. 
8.  All fittings, valves and branch lines must be matched sets all the way along 
the manifold. 
9.  Sufficient space must be left to enable access, servicing or removal of any 
water heater. Outdoor 631 265 models must be spaced at minimum 
920 mm centres to provide the required clearance between flue terminals. 
10. The temperature pressure relief valve drain line from each water heater can 
terminate at a common tundish (funnel) with a visible air break at each drain 
discharge point (refer to the 
diagram on page 
33 and to 
“Relief Drain Line”
 
on page 27). 
Refer to the 
diagrams on pages 
33
 to 
36 for installation and plant layout details.