INSTALLATION 
15 
INDOOR INSTALLATION 
A secondary flue must be installed with an indoor water heater to discharge 
combustion products outside the building. The flue must be self supporting and 
not impose a load on the water heater. Use a slip joint or similar to allow for 
disconnection. There must be a vertical rise of 600 mm from the draught 
diverter before changing direction. The flue design and installation must comply 
with AS 5601. 
 
For indoor models the distances set 
out in the diagram should be observed. 
Keep the water heater and flue at least 
25 
mm clear of walls, cupboards, 
timber or any other combustibles and 
at least 500 mm clear of curtains and 
furnishings. 
 
The water heater is to be installed at 
floor level and must stand vertically 
upright. There are special 
requirements in AS 
5601 for water 
heaters installed in a garage, an 
enclosed space and other locations. 
Remember all local authorities have 
regulations about putting water heaters 
into roof spaces. 
 
If installed in a cupboard, an adequate 
air supply must be provided. For 
efficient water heater operation allow a 
free open space at both the top and 
bottom of the access door, each of at 
least: 
• 
30,000 mm
2
 for a 50 MJ model 
 
SAFE TRAY 
It is a requirement of AS/NZS 3500.4 
that for a new installation, a water 
heater be installed in a safe tray where 
in the event of a leak, property may 
otherwise be damaged. Construction, 
installation and draining of a safe tray 
must comply with the abovementioned 
Standard.