Gas pIpInG
Make sure gas supplied is same type listed on model rating plate. 
The inlet gas pressure must not exceed 14 inch water column (3.5 
kPa)  for  natural  and  propane  gas  (L.P.). The  minimum  inlet  gas 
pressure  shown  on  rating  plate  is  that  which  will  permit  firing  at 
rated input.
sedIMent traps
A sediment trap shall be installed as close to the gas inlet of the 
water heater as practical at the time of water heater installation. 
The sediment trap shall be either a tee fitting with a capped nipple 
in  the  bottom  outlet  or  other  device  recognized  as  an  effective 
sediment trap. 
Contaminants  in  the  gas  lines  may  cause  improper  operation 
of  the  gas  control  valve  that  may  result  in  fire  or  explosion. 
Before attaching the gas line be sure that all gas pipe is clean 
on  the  inside.  To  trap  any  dirt  or  foreign  material  in  the  gas 
supply line, a drip leg (sometimes called a sediment trap) must 
be  incorporated  in  the  piping.  The  drip  leg  must  be  readily 
accessible. Install in accordance with the “Gas Piping” section. 
Refer to the current edition of the National Fuel Gas Code (ANSI 
Z223.1/NFPA 54).
Use pipe joint compound or teflon tape marked as being resistant 
to the action of petroleum [Propane (L.P.)] gases. 
The  water  heater  and  its  gas  connection  must  be  leak  tested 
before placing the water heater in operation.
The  water  heater  and  its  individual  Shut-off  valve  shall  be 
disconnected  from  the  gas  supply  piping  system  during  any 
pressure testing of that system at test pressures in excess of 1/2 
pound per square inch (3.5 kPa). It shall be isolated from the gas 
supply  piping  system  by  closing  its  individual  manual  Shut-off 
valve during any pressure testing of the gas supply piping system 
at test pressures equal to or less than 1/2 pound per square inch 
(3.5 kPa).
IMPORTANT: MAKE SURE THE GAS LINE IS PIPED IN WITH 
HARD PIPE. AvOID FLEX LINE CONSTRUCTION FOR GAS 
DUE TO POSSIBLE GAS FLOW PROBLEMS..
supplY Gas reGulator
The maximum allowable gas supply pressure for this water heater 
is 14 inches W.C. (3.5 kPa). Install a positive lock-up gas pressure 
regulator in the gas supply line if inlet gas pressure can exceed 14 
inches W.C. (3.5 kPa) at any time.
If a positive lock-up regulator is required follow these instructions:
1. Positive  lock-up  gas  pressure  regulators  must  be  rated  at  or 
above the input Btu/hr rating of the water heater they supply.
2. Positive  lock-up  gas  pressure  regulator(s)  should  be  installed 
no closer than 3 feet (1 meter) and no farther than 8 feet (2.4 
meters) from the water heater’s inlet gas connection.
3. After installing the positive lock-up gas pressure regulator(s) an 
initial nominal supply pressure setting of 7.0” W.C. while the water 
heater is operating is recommended and will generally provide 
good water heater operation. Some additional adjustment may 
be required later to maintain a steady gas supply pressure. 
4. When installing multiple water heaters in the same gas supply 
system  it  is  recommended  that  individual  positive  lock-up  gas 
pressure regulators be installed at each unit.
All gas piping must comply with local codes and ordinances or with 
the current edition of National Fuel Gas Code (ANSI Z223.1/ NFPA-
54).  Copper  or  brass  tubing  and  fittings  (except  tin  lined  copper 
tubing) shall not be used.
If the gas control valve is subjected to pressures exceeding 1/2 psi 
(3.5 kPa), the damage to the gas control valve could result in a fire 
or explosion from leaking gas.
If the main gas line Shut-off serving all gas appliances is used, also 
turn “off” the gas at each appliance.  Leave all gas appliances shut 
“off” until the water heater installation is complete.
A  gas  line  of  sufficient  size  must  be  run  to  the  water  heater.  
Consult  the  current  edition  of  National  Fuel  Gas  Code  
(ANSI  Z223.1/NFPA  54)  and  your  gas  supplier  concerning  pipe 
size.
There must be:
•  A readily accessible manual shut off valve in the gas supply line 
serving the water heater, and
•  A drip leg (sediment trap) ahead of the gas control valve to help 
prevent dirt and foreign materials from entering the gas control 
valve.
•  A ground joint union of proper size between the shut off valve and 
control valve to permit servicing of the unit.
Be  sure  to  check  all  the  gas  piping  for  leaks  before  lighting  the 
water  heater.  Use  a  soapy  water  solution,  not  a  match  or  open 
flame. Rinse off soapy solution and wipe dry.
condensate pIpInG
This water heater is a condensing unit and requires a drain to be 
located in close proximity to allow the condensate to drain safely. 
The condensate drains from the unit at the exhaust tee located at