ventInG
Never operate the water heater unless it is vented to the outdoors.
The  instructions  in  this  section  of  the  manual  must  be  followed 
to  avoid  choked  combustion  or  recirculation  of  flue  gases.  Such 
conditions cause sooting of the combustion chamber, burners and 
flue tubes and creates a risk of asphyxiation.
For direct vent application where combustion air might be supplied 
from  extremely  cold  ambient  through  fresh  air  intake  piping 
system, it is recommended that a backflow preventer be installed 
at the intake vent terminal close to the blower before proceeding 
with installation of the rest of the fresh air intake piping. Call the 
technical support phone number listed on the back cover of this 
manual for more information.
vent pIpe terMInatIon
The first step is to determine where the vent pipe will terminate. 
See Figures 15, 16, 17 and 18. The vent may terminate through a 
sidewall as shown in Figures 15 and 16 or through the roof as shown 
in Figures 17 and 18.
The  vent  system  must  terminate  so  that  proper  clearances  are 
maintained  as  cited  in  local  codes  or  the  current  edition  of  the 
National  Fuel  Gas  Code,  (ANSI  Z223.1,  12.9.1  through  12.9.4). 
See Figures 13 and 14.
Instructions on proper installation through a sidewall are provided 
in Figures 15A, 15B, 15C, and 16.
Plan the vent system layout so that proper clearances are maintained 
from plumbing and wiring.
Vent  pipes  serving  power  vented  appliances  are  classified  by 
building  codes  as  “vent  connectors”.  Required  clearances  from 
combustible  materials  must  be  provided  in  accordance  with 
information in this manual under FACTS TO CONSIDER ABOUT 
LOCATION and INSTALLING THE WATER HEATER, and with the 
National Fuel Gas Code and local codes.
plannInG the vent sYsteM
Plan the route of the vent system from the exhaust elbow to the 
planned location of the vent terminal.
1. Layout total vent system to use a minimum of vent pipe and elbows.
2. This water heater is capable of venting  flue gases equivalent to 
45’ (13.7 m) of 2” pipe, 128’ (39 m) of 3” pipe as listed in Table 5.
table 5
number of 
90° elbows
2” Maximum 
pipe - ft. (m)
3” Maximum 
pipe - ft. (m)
1
40 (12.19)
120 (36.57)
2
35 (10.66)
115 (35.05)
3
30 (9.14)
110 (33.52)
4
25 (7.62)
105 (32)
5
20 (6.09)
100 (30.48)
6
15 (4.57)
95 (28.95)
The minimum vent length for each pipe size is one 90° plus 2’ (61 
cm) of straight pipe and the appropriate termination.
note:    The  equivalent  feet  (m)  of  pipe  listed  above  are 
exclusive  of    the    termination.  That  is,  the  termination,  with 
an installed screen, is assumed to be in the system and the 
remainder of the system must not exceed the lengths discussed 
above.
3. The exhaust elbow assembly is designed to accept only straight 
sections of 2” pipe. To start, a minimum 2” (5.1cm) maximum 
6” long of 2” pipe must be inserted and glued to the exhaust 
elbow assembly if utilizing 3” vent pipe. Use the same method 
with the blower inlet if a direct vent configuration is utilized.
If using 2” inch vent pipe:
A minimum of 2” (5.1cm) diameter vent pipe must be attached 
to the exhaust elbow assembly. The total system cannot exceed 
the lengths discussed above, where each elbow is equal to 5 
equivalent feet (1.5m) of straight pipe.
If using 3” inch vent pipe:
Two inches (5.1cm) of 2” pipe must be attached to the exhaust 
elbow assembly before adding a reducer to acquire the desired 
pipe diameter. An appropriately sized 45 degree elbow (supplied 
locally-a schedule 40 DWV) vent terminal must be obtained with 
an  equivalent  screen  (supplied  in  vent  kit).  The  total  system 
cannot  exceed  the  equivalent  pipe  lengths  discussed  above 
where each elbow is equal to 5 feet (1.5m) of straight pipe (3” 
vent pipe).
note:  This  unit  can  be  vented  with  PVC  pipe  materials 
(DWV  ASTM-D2665  or  CSA  B181.2;  Schedule  40,  80,  120 
ASTM-D1785 or CSA B137.3; or SDR Series ASTM-D2241 or 
CSA B137.3), CPVC pipe materials (CPVC41 ASTM-D2846 or 
CSA B137.6; Schedule 40, 80 ASTM-F441 or CSA B137.6; or 
SDR  Series  ASTM-F442),  ABS  pipe  materials  (Schedule  40 
DWV  ASTM-D2661  or  CSA  B181.1.  The  fittings,  other  than 
the TERMINATION should be equivalent to PVC-DWV fittings 
meeting  ASTM  D-2665  (Use  CPVC  fittings,  ASTM  F-438  for 
CPVC  pipe  and  ABS  fittings,  ASTM  D-2661/3311  for  ABS 
pipe). If CPVC or ABS pipe and fittings are used, then proper 
cement must be used for all joints, including joining the pipe 
to Termination (PVC Material). If local codes do not allow the 
use of the PVC termination when a material other than PVC is 
used for venting, then an equivalent fitting of that material may 
be substituted if the screen in the PVC terminal is removed and 
inserted into the new fitting.