13. CHARACTERISTICS 
 
(2) Heat dissipation area for enclosed servo amplifier 
The enclosed control box (hereafter called the control box) which will contain the servo amplifier 
should be designed to ensure that its temperature rise is within  10   ( 50 ) at the ambient 
temperature of 40   (104 ). (With a 5  (41 ) safety margin, the system should operate within a 
maximum 55  (131 ) limit.) The necessary enclosure heat dissipation area can be calculated by 
Equation 13.1. 
 
P
A K T............................................................................................................................................. (13.1) 
where, A 
: Heat dissipation area [m
2
 
: Loss generated in the control box [W] 
 
T  : Difference between internal and ambient temperatures [ ] 
 
K  : Heat dissipation coefficient [5 to 6] 
 
When calculating the heat dissipation area with Equation 13.1, assume that P is the sum of all losses 
generated in the enclosure. Refer to Table 13.1 for heat generated by the servo amplifier. "A" indicates 
the effective area for heat dissipation, but if the enclosure is directly installed on an insulated wall, 
that extra amount must be added to the enclosure's surface area. 
The required heat dissipation area will vary wit the conditions in the enclosure. If convection in the 
enclosure is poor and heat builds up, effective heat dissipation will not be possible. Therefore, 
arrangement of the equipment in the enclosure and the use of a cooling fan should be considered. 
Table 13.1 lists the enclosure dissipation area for each servo amplifier when the servo amplifier is 
operated at the ambient temperature of 40  (104 ) under rated load. 
(Outside)
(Inside)
Air flow
 
Fig. 13.2 Temperature distribution in enclosure 
 
When air flows along the outer wall of the enclosure, effective heat exchange will be possible, because 
the temperature slope inside and outside the enclosure will be steeper.