15. COMMUNICATION FUNCTIONS 
 
15.12.6 Disable/enable of I/O devices (DIO) 
Inputs can be disabled independently of the I/O devices ON/OFF. When inputs are disabled, the input 
signals (devices) are recognized as follows. Among the input devices, EMG, LSP and LSN cannot be 
disabled. 
Signal Status 
Input devices (DI) 
OFF 
External analog input signals 
0V 
Pulse train inputs 
None 
 
(1) Disabling/enabling the input devices (DI), external analog input signals and pulse train inputs with 
the exception of EMG, LSP and LSN. 
Transmit the following communication commands. 
(a) Disable 
Command Data 
No. 
Data 
[9][0] [0][0] 
1EA5 
 
(b) Enable 
Command Data 
No. 
Data 
[9][0] [1][0] 
1EA5 
 
(2) Disabling/enabling the output devices (DO) 
Transmit the following communication commands. 
(a) Disable 
Command Data 
No. 
Data 
[9][0] [0][3] 
1EA5 
 
(b) Enable 
Command Data 
No. 
Data 
[9][0] [1][3] 