15. COMMUNICATION FUNCTIONS 
 
15.12.10 Alarm history 
(1) Alarm No. read 
Read the alarm No. which occurred in the past. The alarm numbers and occurrence times of No.0 (last 
alarm) to No.5 (sixth alarm in the past) are read. 
(a) Transmission 
Send command [3][3] and data No. [1][0] to [1][5]. Refer to section 15.11.1. 
 
(b) Reply 
The alarm No. corresponding to the data No. is provided. 
Alarm No. is transferred in decimal.
0 0
 
For example, "0032" means AL.32 and "00FF" AL._ (no alarm). 
 
(2) Alarm occurrence time read 
Read the occurrence time of alarm which occurred in the past. 
The alarm occurrence time corresponding to the data No. is provided in terms of the total time 
beginning with operation start, with the minute unit omitted. 
(a) Transmission 
Send command [3][3] and data No. [2][0] to [2][5]. 
Refer to section 15.11.1. 
 
(b) Reply 
The alarm occurrence time is transferred in decimal.
Hexadecimal must be converted into decimal.
 
For example, data [0][1][F][5] indicates that the alarm occurred 501 hours after start of operation. 
 
(3) Alarm history clear 
Erase the alarm history. 
Send command [8][2] and data No. [2][0]. 
Command Data 
No. 
Data 
[8][2] [2][0]  1EA5