4 -  3 
4. OPERATION 
 
(2) Startup procedure 
(a) Power on 
1) Switch off the servo-on (SON). 
2) When main circuit power/control circuit power is switched on, "PoS" (Current position) appears 
on the servo amplifier display. 
  In the absolute position detection system, first power-on results in the absolute position lost 
(AL.25) alarm and the servo system cannot be switched on. This is not a failure and takes place 
due to the uncharged capacitor in the encoder. 
  The alarm can be deactivated by keeping power on for a few minutes in the alarm status and 
then switching power off once and on again. 
  Also in the absolute position detection system, if power is switched on at the servo motor speed 
of 500r/min or higher, position mismatch may occur due to external force or the like. Power must 
therefore be switched on when the servo motor is at a stop. 
 
(b) Test operation 
Using jog operation in the "test operation mode" of the MR Configurator (servo configuration 
software), confirm that the servo motor operates at the slowest speed. (Refer to section 6.7.1, 7.9.2) 
 
(c) Parameter setting 
Set the parameters according to the structure and specifications of the machine. Refer to chapter 5 
for the parameter definitions and to sections 6.4 and 7.6 for the setting method. 
Parameter Name  Setting 
Description 
No.0 
Command system, regenerative 
option selection 
No.1 
Feeding function selection 
No.2 
Function selection 1 
20
Absolute value command system.
MR-RB032 regenerative option is used.
10
When forward rotation start (ST1) is
valid, address is incremented in CCW
direction.
Since command resolution is 10 times, 
feed length multiplication factor of 10
times is selected.
Absolute position detection system.
1
No.4 
Electronic gear numerator (CMX) 
32768 
From calculation result of formula (4.1) 
No.5 
Electronic gear denominator (CDV) 
1250 
From calculation result of formula (4.1) 
After setting the above parameters, switch power off once. Then switch power on again to make the 
set parameter values valid. 
 
(d) Point table setting 
Set the point table according to the operation pattern. Refer to section 4.2 for the point table 
definitions and to sections 6.5 and 7.5 for the setting method. 
Position data 
[ 10
STM
m] 
Servo motor 
speed [r/min] 
Acceleration time 
constant [ms] 
Deceleration time 
constant [ms] 
Dwell [ms] 
Auxiliary 
function 
20000 2500 
200 
300 
0 0 
 
(e) Servo-on 
Switch the servo-on in the following procedure. 
1) Switch on main circuit/control circuit power. 
2) Switch on the servo-on (SON). 
 
When placed in the servo-on status, the servo amplifier is ready to operate and the servo motor is 
locked. By using the sequence in the diagnostic mode in section 7.3, the ready status can be shown 
on the servo amplifier display. In the operation-ready status, the following screen appears.