4 -  26 
4. SIGNALS AND WIRING 
 
Device Symbol 
Connector 
pin No. 
Functions/Applications 
Zero speed 
ZSP 
 
ZSP turns on when the servo motor speed is zero speed (50r/min) or less. Zero 
speed can be changed using parameter No.PC17. 
Example 
Zero speed is 50r/min 
OFF
ON
0r/min
1)
3)
2)
4)
Forward 
rotation 
direction
Servo motor 
speed
Reverse 
rotation 
direction
zero speed 
(ZSP)
ON level
50r/min
OFF level
70r/min
ON level
50r/min
OFF level
70r/min
Parameter 
No.PC17
20r/min
(Hysteresis width)
20r/min
(Hysteresis width)
Parameter 
No.PC17
 
ZSP turns on 1) when the servo motor is decelerated to 50r/min, and ZSP turns 
off 2) when the servo motor is accelerated to 70r/min again. 
ZSP turns on 3) when the servo motor is decelerated again to 50r/min, and turns 
off 4) when the servo motor speed has reached -70r/min. 
The range from the point when the servo motor speed has reached ON level, and 
ZSP turns on, to the point when it is accelerated again and has reached OFF 
level is called hysteresis width. 
Hysteresis width is 20r/min for this servo amplifier. 
Variable gain selection 
CDPS 
 
CDPS is on during gain changing. 
Note. These are pin Nos. assigned at default. 
 
4.5.2 Input signals 
Device Symbol 
Connector 
pin No. 
Functions/Applications 
PP CN6-6 
Manual pulse generator 
NP CN6-19 
Used to connect the manual pulse generator (MR-HDP01). (Refer to section 
14.18.) 
 
4.5.3 Output signals 
Refer to section 4.8.2 for the output interfaces (symbols in the I/O Division field in the table) of the 
corresponding connector pins. 
 
Signal Symbol 
Connector 
pin No. 
Functions/Applications 
I/O 
division 
Encoder A-phase pulse 
(differential line driver) 
LA 
LAR 
CN6-11 
CN6-24 
Encoder B-phase pulse  
(differential line driver) 
LB 
LBR 
CN6-12 
CN6-25 
Outputs pulses per servo motor revolution set in parameter No.PA15 
in the differential line driver system. In CCW rotation of the servo 
motor, the encoder B-phase pulse lags the encoder A-phase pulse 
by a phase angle of  /2. 
The relationships between rotation direction and phase difference of 
the A- and B-phase pulses can be changed using parameter No. 
PC19. 
DO-2 
Encoder Z-phase pulse 
(differential line driver) 
LZ 
LZR 
CN6-13 
CN6-26 
Outputs the zero-point signal of the encoder in the differential line 
driver system. One pulse is output per servo motor revolution. This 
signal turns on when the zero-point position is reached. (Negative 
logic) 
The minimum pulse width is about 400 s. For home position return 
using this pulse, set the creep speed to 100r/min. or less. 
DO-2