6. PARAMETERS 
 
No.  Symbol 
Name and function 
Initial value 
Unit 
Setting range
PC10 
 
ZTT 
 
 
Stopper type home position return torque limit value 
Used to set the torque limit value relative to the max. torque in [%] in stopper 
type home position return. (Refer to section 5.6.5.) 
15.0 %  1 
to 
100.0 
PC11 
 
CRP 
 
 
Rough match output range 
Used to set the command remaining distance range where the rough match 
(RXn2) is output. 
10
STM
m 0 
to 
65535 
PC12 
 
JOG 
 
Jog speed 
Used to set the jog speed command. 
100 r/min  0 
to permissible 
speed 
PC13 
 
*STC  S-pattern acceleration/deceleration time constant 
Set when inserting S-pattern time constant into the acceleration/deceleration 
time constant of the point table. (Refer to section 6.3.3.) 
This time constant is invalid for home position return. 
0 ms  0 
to 
1000 
PC14 
 
*BKC 
 
Backlash compensation 
Used to set the backlash compensation made when the command 
direction is reversed. 
This function compensates for the number of backlash pulses in the 
opposite direction to the home position return direction. 
For the home position ignorance (servo-on position as home position), this 
function compensates for the number of backlash pulses in the opposite 
direction to the first rotating direction after establishing the home position 
by switching ON the servo-on (RYn0). 
In the absolute position detection system, this function compensates for 
the backlash pulse count in the direction opposite to the operating direction 
at power-on. 
0 pulse  0 
to 
32000 
PC15 
 
 
For manufacturer setting 
Do not change this value by any means. 
0000h  
 
PC16 
 
MBR 
 
Electromagnetic brake sequence output 
Used to set the delay time (Tb) between when the electromagnetic brake 
interlock (MBR) switches off and when the base circuit is shut off. 
100 ms  0 
to 
1000 
PC17 
 
ZSP 
 
Zero speed 
Used to set the output range of the zero speed (ZSP). 
Zero speed signal detection has hysteresis width of 20r/min. 
50 r/min  0 
to 
10000 
PC18 
 
*BPS 
 
Alarm history clear 
Used to clear the alarm history. 
Alarm history clear
0: Invalid
1: Valid
When alarm history clear is made valid,
the alarm history is cleared at next power-on.
After the alarm history is cleared, the setting 
is automatically made invalid (reset to 0).
0 0 0
 
0000h  Refer 
to 
name and 
function 