14. OPTIONS AND AUXILIARY EQUIPMENT 
 
14.15 Noise reduction techniques 
Noises are classified into external noises which enter the servo amplifier to cause it to malfunction and those 
radiated by the servo amplifier to cause peripheral devices to malfunction. Since the servo amplifier is an 
electronic device which handles small signals, the following general noise reduction techniques are required. 
Also, the servo amplifier can be a source of noise as its outputs are chopped by high carrier frequencies. If 
peripheral devices malfunction due to noises produced by the servo amplifier, noise suppression measures 
must be taken. The measures will vary slightly with the routes of noise transmission. 
 
(1) Noise reduction techniques 
(a) General reduction techniques 
Avoid laying power lines (input and output cables) and signal cables side by side or do not bundle 
them together. Separate power lines from signal cables. 
Use shielded, twisted pair cables for connection with the encoder and for control signal transmission, 
and connect the shield to the SD terminal. 
Ground the servo amplifier, servo motor, etc. together at one point (refer to section 4.12). 
 
(b) Reduction techniques for external noises that cause the servo amplifier to malfunction 
If there are noise sources (such as a magnetic contactor, an electromagnetic brake, and many relays 
which make a large amount of noise) near the servo amplifier and the servo amplifier may malfunction, 
the following countermeasures are required. 
Provide surge absorbers on the noise sources to suppress noises. 
Attach data line filters to the signal cables. 
Ground the shields of the encoder connecting cable and the control signal cables with cable clamp 
fittings. 
Although a surge absorber is built into the servo amplifier, to protect the servo amplifier and other 
equipment against large exogenous noise and lightning surge, attaching a varistor to the power input 
section of the equipment is recommended.