Справочник Пользователя для Mitsubishi Electronics QD64D2

Скачать
Страница из 154
8
TROUBLESHOOTING
8.2 When the QD64D2 does not Start Counting
8
 - 4
1
O
V
ER
VI
E
W
2
S
YST
EM
 
CONF
IGURA
T
ION
3
S
P
E
C
IF
ICA
T
IONS
4
P
R
O
C
EDURES
 AND 
S
E
T
T
INGS
 B
E
F
O
RE
 
OP
E
R
A
T
ION
5
F
UNCT
IONS
6
UT
IL
IT
Y
 P
A
CK
A
G
E
 (
G
X
 
C
onfi
gurato
r-C
T
)
7
P
R
OGRA
M
MING
8
TR
O
U
BL
ESHO
O
T
IN
G
8.2
When the QD64D2 does not Start Counting
8.3
When the QD64D2 does not Normally Count
Table 8.6 When the QD64D2 does not start counting
Check item
Action
Reference
Do the LEDs of  A and  B turn ON by directly 
applying a voltage to the pulse input terminals of 
A and  B using such as a voltage stabilizer?
If they turn ON, check the external wiring, encoder 
side and so on,  and correct the error. 
If they remain OFF, it is a hardware failure. Please 
consult your local Mitsubishi representative, 
explaining a detailed description of the problem.
Is the external wiring of  A and  B correct?
Check the external wiring and correct the error. 
Is the count enable command (Y06) turned ON?
Turn ON the count enable command (Y06) by the 
sequence program.
Are the pulse input method and pulse input mode 
set with the intelligent function module switch 
setting the same?
Match the pulse input method with the pulse input 
mode made on the intelligent function module 
switch setting. 
Table 8.7 When the QD64D2 does not normally count
Check item
Action
Reference
Does the input pulse waveform meet the 
performance specifications? 
Check the pulse waveform with a synchronoscope. 
When the input pulse does not meet the 
performance specifications, input the pulse which 
meets the performance specifications. 
When the count value that is same with another 
channel is input, does the count result become 
the same with that of another channel?
If they differ, it is a hardware failure. Please consult 
your local Mitsubishi representative, explaining a 
detailed description of the problem. 
----
Noise 
reduction 
measures
Are the shielded twisted pair cables 
used for pulse input wiring?
Use the shielded twisted pair cables for pulse input 
wiring. 
Has the measures against noise been 
taken to the adjacent devices and 
inside the control panel? 
Take noise reduction measures such as attaching 
a CR surge suppressor to the magnet switch.
Is the distance between the high 
voltage equipment and pulse input 
line kept enough?
Bundle the pulse input lines and put them in a 
single tube, and keep a distance of 150mm (5.91 
inch) or more with the power line even inside the 
control panel.
Does any noise come from the ground 
part of the QD64D2? 
Separate the ground cable of the QD64D2 from the 
ground part.
If the QD64D2 case touches to the ground part, 
separate it. 
Are the count value data treated in 32-bit binary in 
the sequence program?
Correct the sequence program so that the count 
value data can be treated in 32-bit binary.
Is the preset performed out of the count range of 
the ring counter? 
(Only for the ring counter function)
Perform the preset within the count range of the 
ring counter.