T
IN
G
8.5
When the Counter Value Coincidence No.1 (X02) or Counter 
Value Coincidence No.2 (X05) are Turned ON, but the 
Coincidence Output No.1 Terminal (EQU1) and Coincidence 
Output No.2 Terminal (EQU2) do not Turn ON
8.6
When the Coincidence Detection Interrupt does not Occur
Table 8.11 When the counter value coincidence No.1 (X02) or counter value coincidence No.2 (X05) are turned ON but the 
coincidence output No.1 terminal (EQU1) and coincidence output No.2 terminal (EQU2) do not turn ON
Check item
Action
Reference
Is the coincidence output enable command (Y03) 
turned ON? 
(Only for the coincidence output function)
Turn ON the coincidence output enable command 
(Y03). 
Is a voltage applied to the external coincidence 
output power supply terminal.
Apply a voltage to the external coincidence output 
power supply terminal. 
Is the fuse blown? 
If the FUSE LED is ON, the fuse is blown. 
Please consult your local Mitsubishi 
representative, explaining a detailed description of 
the problem.
Is the external wiring of the coincidence output 
No.1 terminal (EQU1) and coincidence output 
No.2 terminal (EQU2) correct?
Check the external wiring and correct the error. 
Table 8.12 When the coincidence detection interrupt does not occur
Check item
Action
Reference
Does the CPU module support the coincidence 
detection interrupt function? 
Change the CPU module to the one which 
supports the intelligent function module event 
interrupt. 
If the setting made on [Interrupt pointer setting] of 
[Intelligent function module setting ] in [PLC 
parameter] correct? 
Check the intelligent function module interrupt 
pointer setting.
Is the way to use the program execution control 
instruction, such as IMASK, correct? 
Check the sequence program. 
Is the counter value coincidence (X02 and X05) 
still ON?
(Only for the coincidence output function) 
Reset (OFF) the counter value coincidence No.m 
(X02 and X05) by the coincidence signal No.m 
reset command (Y01 and Y02) for the 
corresponding number.