Справочник Пользователя для Mitsubishi Electronics QD64D2

Скачать
Страница из 154
5
 - 26
5.3 Using the Counter Value Comparison Function
5.3.4 Coincidence detection interrupt function
5
FUNCTIONS
POINT
 • Coincidence detection interrupt occurs at the rising edge (OFF
ON) of 
the counter value coincidence No.1 (X02) or the counter value 
coincidence No.2 (X05). Therefore, next interrupt request does not occur 
unless the counter value coincidence No.1 (X02) and the counter value 
coincidence No.2 (X05) are reset and turned OFF. 
 • When using the coincidence output function, the counter value 
coincidence No.1 (X02) and the counter value coincidence No.2 (X05) 
turns ON immediately after the power-on or resetting the programmable 
controller CPU; however, a coincidence detection interrupt does not 
occur.  
For resetting method of the counter value coincidence No.1 (X02) and the 
counter value coincidence No.2 (X05), refer to Section 5.3.1.